– Indoor units can be changed in turn according to the stoppage rate set for each group.
0% 10%
30%20%
*The indoor unit operation stoppage rate can be selected from 10% to 30%.
Time Time
Electric power
Electric power
With controlWithout control
Group A Group B
Group C
Group D
• Outdoor unit capacity saving
The power consumption is reduced by limiting the upper limit of the outdoor unit capacity for each
refrigerant system.
This has a reducing effect especially in the summer, winter and other times when the heat load is
high.
In addition, because the upper limit capacity of the outdoor unit is limited directly, it is a control
which easily exhibits an energy saving effect compared to rotation control. However, because the
outdoor unit does not operate above the limited capacity, there may be a loss of comfort, depend-
ing on the indoor heat load. (The operation capacity upper limit rate [%] of the outdoor unit is spec-
ified for each refrigerant system.)
100
% kW
T
ime
50
70
0 0
Outdoor unit capacity
Indoor heat load
Indoor
heat load
Maximum capacity of outdoor unit
2-25. Energy saving setting on System controller - (07-132) - 2. Function settings