When electricity meter used is specified by pulse constant
The connection configuration is shown below.
For the electricity meter specified by pulse constant, the power consumption indicated by output
pulse must be corrected by VT/CT ratio. In this case, the settings are as follows:
Set point Set item Set value Description Remarks
Electricity
meter
Set in accordance
with the product
manual.
When there is a product unique
setting, setting is performed in
accordance with the product
manual. (Pulse constant value,
output coefficient, etc.)
Outdoor
unit
Meter no. setting Arbitrary
Set an unique electricity meter no.
for electricity meter identification.
The information will
become necessary
when setting
System controller
later. Refer also to
"Setting on outdoor
unit PCB" on page
07-60
.
Electricity meter
pulse setting
The pulse
constant value /
(VT ratio × CT
ratio). However,
truncated after
the decimal point
Set the approximate number of
power meter pulses that are
equivalent to 1kWh.
When set number of pulses come
from the electricity meter, the
outdoor unit communicates “1” to
the system controller.
System
controller
Electricity meter
system setting
Units measured
by electricity
meter
Set the outdoor unit and indoor
unit, measured by the electricity
meter of the meter no. set at the
outdoor unit.
The value set by
each outdoor unit is
used.
Pulse setting
(Electricity meter
pulse setting
value) × (VT ratio
× CT ratio) /
pulse constant
Values after the
decimal point
must be also
input.*
Set the standard number of kWh for
the value communicated from the
outdoor unit.
Set the number of kWh that
corresponds to the “1”
communicated from the outdoor
unit.
Refer to the value
set by each outdoor
unit.
*: Input up to 6 decimal digits
[Setting example]
Equipment conditions:
VT ratio=1 (not used), CT ratio=500(2500/5 A), electricity meter=3,200 pulse/kWh
Set value:
Electricity meter pulse setting=6 (3200/ [1 × 500]), Pulse setting=0.9375 (6 × [1 × 500]/3200) For
details, refer to the calculating formula of the table above.
2-26. Electricity charge apportionment setting (System controller, Touch panel
controller)
- (07-151) - 2. Function settings