CN11 and CN12: Apply voltage terminal
When a power supply must be provided at the input device you want to connect, connect to CN11
and CN12.
PCB
3 31 1
*
1
*
3
*
2
*
3
DC power
supply 24 V
CN11
(White)
CN12
(Green)
Connected unit
*
1
:
Make the power supply DC 24 V. Select a power supply capacity with an ample sur-
plus for the connected load.
*
2
:
Do not impress a voltage exceeding 24 V across pin 1-3.
*
3
:
The allowable current is DC 5 mA or less. (Recommended: DC 5 mA)
Provide a load resistance such that the current becomes DC 5
mA or less.
A twisted pair cable 22 AWG (0.33 mm
2
) should be used. (Maximum cable length:
82 ft [25 m])
4-2. Central remote controller (UTY-DCGY) - (08-64) - 4. Controller
EXTERNAL INPUT
AND OUTPUT
EXTERNAL INPUT
AND OUTPUT