¢ External output
Connector Output voltage Status
CN9 (Black)
Ch1 0 V All indoor units: Stop
Pins 3-4 DC 12 V One or more indoor units: Operation
Ch2 0 V Normal
Pins 1-2 DC 12 V Error
Connected load
*
2
C
onnected load
*
2
*
3
Connected unit
DC power supply
12 V *
1
+
+
+
+
-
-
-
-
CN9 (Black)
PCB
134 2
*
1
:
Provide a DC 12 V power supply. Select a power supply capacity with an ample surplus for
the connected load. Do not impress a voltage exceeding 12
V across pins 1-2 and 3-4.
*
2
:
The allowable current is DC15 mA or less. Provide a load resistance such that the current
becomes DC 15 mA or less.
*
3
:
Polarity is “+” for pins 1 and 3, “-” for pins 2 and 4. Connect correctly.
O
peration status (External output 1)
The output for CN9 (3-4) is on when one
or more indoor units are operating.
The output is off when all of the indoor
units are stopped.
Operation
S
top
12 V
0 V
CN9 (3-4)
Output
Indoor unit(s)
E
rror status (External output 2)
The output for CN9 (1-2) is on when an er-
ror is generated at one or more indoor
units, outdoor unit or
Central remote con-
troller.
Error
N
ormal
12 V
0 V
CN9 (1-2)
Output
Indoor unit(s) or
Outdoor unit or
Central R.C.
4-2. Central remote controller (UTY-DCGY) - (08-67) - 4. Controller
EXTERNAL INPUT
AND OUTPUT
EXTERNAL INPUT
AND OUTPUT