12-2 ALPS Advanced Line Protection System
GE Power Management
12.1 INTRODUCTION 12 ASCII COMMUNICATIONS
12
Table 12–2: ASCII COMMAND LIST (Sheet 1 of 5)
ASCII
COMMAND
MNEMONIC
COMMAND DESCRIPTION LOWEST
LEVEL
PASSWORD
NEEDED
RELAY PROMPT USER
RESPONSE
LOGIN Lo
in to the relay NONE Unit ID?
Password?
Reports the access level
ranted
or
that the
password entered is INVALID
Relay ID number;
up to 10 character
password
QUIT Lo
s out from the relay,
displays the relay status,
and returns the privile
e
level to VIEW for the relay
port used.
VIEW Press ENTER to continue
Do you want to lo
out?
You have lo
ed out from the relay
Press the enter
key; Y or N
PASSword Chan
e the passwords
used by ALPS-Link and
ASCII; MMI passwords are
not affected by this
command
Level equal to
the password
bein
chan
ed
Enter Current Password
Enter New Password
Re-enter New Password
Password chan
ed
or
INVALID; password not
chan
ed
old password;
new password;
new password
VALues Display the present values
of volta
es, currents, watts,
Vars, etc., includin
Breaker
Health in the second
screen. Press ENTER to
see the second screen
VIEW
Present Values
VA rms: V
VB rms: V
VC rms: V
VA: V de
s
VB: V de
s
VC: V de
s
Watts: KW
Power Factor
Setting Group Number
:1
Breaker 1: Closed
Breaker Health
Phase A accumulated
Amps: 45.2 A
Phase B accumulated
Amps: 11.1 A
Phase C accumulated
Amps: 25.7A
IA rms: A
IB rms: A
IC rms: A
In rms: A
IA: A de
s
IB: A de
s
IC: A de
s
In: A de
s
Vars: kVar
Frequency: Hz
No. of Breakers: 2
Breaker 2: N/A
Breaker Operations: 129
None
READin
s Display the present values
of volta
es, currents, watts,
Vars, etc., and update them
once per second. The ESC
key stops the update. No
Breaker Health is displayed.
FAUlts Display fault reports. The list
of available faults is
displayed first then a
number is chosen to view a
particular fault
VIEW FLTNO DATE TIME TRIP FAULT DISTANCE
TYPE TYPE
1 07/09/98 EXT AG 0.2mi
15:32:23.6833
Enter Fault Number (press ESC to quit): 1
Report for Fault No: 1
TRIP DATE: 07/03/98
TRIP TIME: 16.32.23.6833
Trip Type(s): Z1
Fault Type: ABG
Relay Operatin
Time: 488 ms
Breaker Operatin
Time: 1152 ms
Distance: 9999 miles
ITEM A B C D
Prefault Current (A) 0.00 0.00 0.00 0.00
Fault Current (A) 0.00 0.00 0.00 0.00
Fault Volta
e (kV) 0.00 0.00 0.00 0.00
Press ENTER to Continue
List of Fault Events:
TIME EVENT
16:32:23.7025 Oscillo
raphy Capture
16:32:23.7041 RMS Oscillo
raphy Data
Press Y to
et oscillo
raphy data
Press ESC to quit
Press Any Key to continue
Press E for
expanded mode,
ESC to end
Two di
it number,
1 to 16