GE Power Management
ALPS Advanced Line Protection System 12-3
12 ASCII COMMUNICATIONS 12.1 INTRODUCTION
12
EVEnts Display events VIEW List of events with date and time. Example:
06/30/98 16:26:29.7562 Host Lo
off on MMI
06/30/98 16:24:37.5944 Host Lo
on OK on Port 2
06/30/98 16:10:45.6505 Recloser in RESET state
06/30/98 16:10:40.0000 Settin
s File 0 in Use
06/30/98 16:10:40.0000 System booted
Press ENTER to continue, B to
o back a screen, or
ESC to quit
None
TRIP Open Breaker command;
issues the command to
open breaker; breaker will
be determined by settin
s
NUM_BRKR and NUM_TC
CONTROL Enter Breaker No. (1 / 2 / BOTH)
TRIP BREAKER 1,! Are you sure? (Y/N)
Breaker open command sent
1, 2, or BOTH;
Y to trip, N to
cancel
CLOSe Close Breaker command;
issues the command to
close breaker; breaker will
be determined by settin
s
NUM_BRKR and NUM_TC
CONTROL Enter Breaker No. (1 / 2 / BOTH)
CLOSE BREAKER 1,! Are you sure? (Y/N)
Breaker close command sent
1, 2, or BOTH;
Y to trip, N to
cancel
ENOUT Enable outputs CONTROL Enable Outputs, Are you sure? (Y/N)
Outputs are disabled
or
Outputs cannot be disabled
Y for OK, N to
cancel; command
DISABle
outputs
Disable outputs CONTROL Disable Outputs, Are you sure? (Y/N)
Outputs are disabled
or
Outputs cannot be disabled
Y for OK, N to
cancel; command
STATUs Display status of the relay VIEW RELAY STATUS
Refer to the servicin
section for status messa
es
for the ALPS
Press ENTER to continue
None
DATAReset Clear various data lo
s
maintained in the relay
SETTING To clear FAULT REPORT and OSCILLOGRAPHY
enter F
To clear OST REPORT enter S
To clear EVENT DATA enter E
To reset tar
et LED and clear warn, failure, and trip
messa
es enter L
To clear BREAKER HEALTH enter B
To quit press ESC
Enter your choice:
Enter letter, press
ENTER
DIGTest Perform Di
ital Output tests;
the test ener
izes the
selected output until END is
chosen or another output is
tested
MASTER Turn Protection off (Y/N):
Enter the number of the Di
ital Output to be tested
(1 to 18)
Enter END to end test
To see list of Di
ital Outputs enter H
To quit press ESC
Enter your choice: 4
Di
ital Output #4 is Activated
Turn Protection on? (Y/N):
Enter letter; Enter
di
it form 1 to 18;
enter letter
GROUP SETTING The active Protectionin
Settin
Group number is 1
To select a Settin
Group enter Settin
Group
Number (‘1’ - ‘4’)
To select active settin
roup throu
h Contact
Converter Inputs enter ‘0’
To quit press ESC
Enter your choice:
Are you sure (Y/N):? y
New Active Group = 3
Enter di
it from 0
to 4; enter letter
INPuts Request contact converter
status
VIEW Contact Converter #0=0 (
SETTING GROUP BIT 0
)
Contact Converter #1=1 (
SETTING GROUP BIT 1
)
Contact Converter #2=1 (not assi
ned)
Contact Converter #3=0 (not assi
ned)
Contact Converter #4=0 (not assi
ned)
Contact Converter #5=1 (not assi
ned)
Contact Converter #6=0 (not assi
ned)
Contact Converter #7=1 (not assi
ned)
None
Table 12–2: ASCII COMMAND LIST (Sheet 2 of 5)
ASCII
COMMAND
MNEMONIC
COMMAND DESCRIPTION LOWEST
LEVEL
PASSWORD
NEEDED
RELAY PROMPT USER
RESPONSE