GE Power Management
ALPS Advanced Line Protection System 12-3
12 ASCII COMMUNICATIONS 12.1 INTRODUCTION
12
EVEnts Display events VIEW List of events with date and time. Example:
06/30/98 16:26:29.7562 Host Lo
g
off on MMI
06/30/98 16:24:37.5944 Host Lo
g
on OK on Port 2
06/30/98 16:10:45.6505 Recloser in RESET state
06/30/98 16:10:40.0000 Settin
g
s File 0 in Use
06/30/98 16:10:40.0000 System booted
Press ENTER to continue, B to
g
o back a screen, or
ESC to quit
None
TRIP Open Breaker command;
issues the command to
open breaker; breaker will
be determined by settin
g
s
NUM_BRKR and NUM_TC
CONTROL Enter Breaker No. (1 / 2 / BOTH)
TRIP BREAKER 1,! Are you sure? (Y/N)
Breaker open command sent
1, 2, or BOTH;
Y to trip, N to
cancel
CLOSe Close Breaker command;
issues the command to
close breaker; breaker will
be determined by settin
g
s
NUM_BRKR and NUM_TC
CONTROL Enter Breaker No. (1 / 2 / BOTH)
CLOSE BREAKER 1,! Are you sure? (Y/N)
Breaker close command sent
1, 2, or BOTH;
Y to trip, N to
cancel
ENOUT Enable outputs CONTROL Enable Outputs, Are you sure? (Y/N)
Outputs are disabled
or
Outputs cannot be disabled
Y for OK, N to
cancel; command
DISABle
outputs
Disable outputs CONTROL Disable Outputs, Are you sure? (Y/N)
Outputs are disabled
or
Outputs cannot be disabled
Y for OK, N to
cancel; command
STATUs Display status of the relay VIEW RELAY STATUS
Refer to the servicin
g
section for status messa
g
es
for the ALPS
Press ENTER to continue
None
DATAReset Clear various data lo
g
s
maintained in the relay
SETTING To clear FAULT REPORT and OSCILLOGRAPHY
enter F
To clear OST REPORT enter S
To clear EVENT DATA enter E
To reset tar
g
et LED and clear warn, failure, and trip
messa
g
es enter L
To clear BREAKER HEALTH enter B
To quit press ESC
Enter your choice:
Enter letter, press
ENTER
DIGTest Perform Di
g
ital Output tests;
the test ener
g
izes the
selected output until END is
chosen or another output is
tested
MASTER Turn Protection off (Y/N):
Enter the number of the Di
g
ital Output to be tested
(1 to 18)
Enter END to end test
To see list of Di
g
ital Outputs enter H
To quit press ESC
Enter your choice: 4
Di
g
ital Output #4 is Activated
Turn Protection on? (Y/N):
Enter letter; Enter
di
g
it form 1 to 18;
enter letter
GROUP SETTING The active Protectionin
g
Settin
g
Group number is 1
To select a Settin
g
Group enter Settin
g
Group
Number (‘1’ - ‘4’)
To select active settin
g
g
roup throu
g
h Contact
Converter Inputs enter ‘0’
To quit press ESC
Enter your choice:
Are you sure (Y/N):? y
New Active Group = 3
Enter di
g
it from 0
to 4; enter letter
INPuts Request contact converter
status
VIEW Contact Converter #0=0 (
SETTING GROUP BIT 0
)
Contact Converter #1=1 (
SETTING GROUP BIT 1
)
Contact Converter #2=1 (not assi
g
ned)
Contact Converter #3=0 (not assi
g
ned)
Contact Converter #4=0 (not assi
g
ned)
Contact Converter #5=1 (not assi
g
ned)
Contact Converter #6=0 (not assi
g
ned)
Contact Converter #7=1 (not assi
g
ned)
None
Table 12–2: ASCII COMMAND LIST (Sheet 2 of 5)
ASCII
COMMAND
MNEMONIC
COMMAND DESCRIPTION LOWEST
LEVEL
PASSWORD
NEEDED
RELAY PROMPT USER
RESPONSE