12-4 ALPS Advanced Line Protection System
GE Power Management
12.1 INTRODUCTION 12 ASCII COMMUNICATIONS
12
MODEL Retrieve the model number,
serial number, and version
of the relay
VIEW MODEL: ALPSDA35U143VE3S
VERSION: V0001.11
None
CRCcalc Recalculates the CRC of
various settin
s
roups (this
is primarily a
troubleshootin
command -
it is used only where a relay
may have
one throu
h a
loss power durin
a settin
s
chan
e, and the settin
s
are corrupted beyond the
ability of the relay to
correct).
SETTINGS CRCs are recalculated None
STLINID Allows the station and line
IDs to be chan
ed
SETTINGS Station ID: Current Station ID
Line ID: Current Line ID
Do you want to chan
e Station and/or
Line ID? (Y/N): y
Enter new Station ID (max. 32 characters): NEW
STATION ID
Enter new Line ID (max. 32 characters): NEW
FEEDER ID
Are you sure? (Y/N): y
Y to chan
e, N to
exit; NEW
STATION ID or
ENTER to keep
current ID; NEW
FEEDER ID or
ENTER to keep
current ID; enter
letter
RELTest Selects and runs a
iven
relay test. Puts the relay in
test mode (Contact A!
Reports test function
operation).
MASTER Disable Outputs? (Y/N):
Select the function to be tested (2 to 49)
To stop the test in pro
ress enter I
To see the list of functions enter H
To quit without suspendin
the test enter Q
To quit press ESC
Enter your choice: 2
Z1 AG test function is routed to contact A!
Enter letter Y or
N; one to two di
it
number, 1 to 49;
enter letter H or Q
ACCESS Allows the user to chan
e
privile
e level
VIEW Enter Password:? User-defined
password
OSCtr
Start oscillo
raphy
recordin
VIEW Are you sure? (Y/N): y
Oscillo
raphy is tri
ered
Enter letter Y or N
CHNLtest Test PLC channel. The test
starts when a B is entered
and ends only when an E is
entered.
MASTER To be
in Channel Test enter B, To end Channel Test
enter E
Enter letter B or E
PLAYBack Re-run a fault produced
earlier or test case for relay.
There are three choices for
runnin
a fault: 1) re-run a
fault saved in the relay; 2)
with factory test data; 3)
download oscillo
raphy into
relay and run fault
ACTION To run the relay on Fault Data enter Fault Number
To run the relay on factory test case enter F
To run the relay on downloaded test data enter D
To quit press ESC
Enter your choice: 5
The fault is absent
There is no factory test data in the relay
There is no downloaded data in the relay
Fault number, F,
D, or ESC
LUIPass Display coded LUI
passwords. See decodin
table in Chapter 8
VIEW MMI PASSWORDS
Settin
s Password: [DHLPPPPPPPPPPPP
Control Password: [AEIPPPPPPPPPPPP
Master Password: [MBFPPPPPPPPPPPP
None
HELP Displays the ASCII
command mnemonics as
well as descriptions of each
command
VIEW None
Table 12–2: ASCII COMMAND LIST (Sheet 3 of 5)
ASCII
COMMAND
MNEMONIC
COMMAND DESCRIPTION LOWEST
LEVEL
PASSWORD
NEEDED
RELAY PROMPT USER
RESPONSE