ADV100 • Functions description and parameters list 123
26–APPLICATION
This menu is designed to host two applications using the MDPlc program.
It will not be possible to use both applications simultaneously.
The 558Applicationselectparameter in the DRIVE CONFIG menu must be used to select between the two possible
applications.
ADV100PIDHVACapplication
REFERENCES
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
11000 Setpointsel ENUM Disable PID -1 4174 RWZ FVS
Parameter for selecting the PID input reference. If you select PID disabilit [-1] the ramp reference and thus the drive
speed depend on the standard selections in the REFERENCES menu. For the other selections the parameters in
the REFERENCES menu are modied so that the ramp reference corresponds to the value of the PIDoutput [3700]
variable.
If you select DigitalParam [0] the PID reference corresponds to the value of parameter 11002 Setpointsel. One of
the following values can be set:
-1 Disable PID
0 Digital Param
1600 Analog inp 1X
1650 Analog inp 2X
3700 PID output
3710 Pad 6
3712 Pad 7
3714 Pad 8
3716 Pad 9
3718 Pad 10
3720 Pad 11
3722 Pad 12
3724 Pad 13
3726 Pad 14
3728 Pad 15
3730 Pad 16
4024 FieldbusM->S1
4034 FieldbusM->S2
4044 FieldbusM->S3
4054 FieldbusM->S4
4064 FieldbusM->S5
4074 FieldbusM->S6
4084 FieldbusM->S7
4094 FieldbusM->S8
4104 FieldbusM->S9
4114 FieldbusM->S10
4124 FieldbusM->S11
4134 FieldbusM->S12
4144 FieldbusM->S13
4154 FieldbusM->S14
4164 FieldbusM->S15
4174 FieldbusM->S16
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
11002 Setpointval FLOAT 0 0 0 RW FVS
If parameter 11000 Setpointval is set to DigitalParam [0] the PID input reference value can be written in this
parameter. For the other selections of parameter 11000 Setpointval this parameter displays the value of the cur-
rent reference, scaled according to parameters 11012 Signalsfullscale and 11014 Signalsoffsetand to the unit of