38 ADV100 • Functions description and parameters list
9–JOGFUNCTION
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
9.1 910 Jogsetpoint rpm INT16 0 CALCI CALCI RW FVS
The reference for Jog mode operation. This reference can also be set via an analog input. The Jog reference is
enabled when the signal used for the Jog+or Jog– command is enabled, the Run command is not present and the
drive output frequency is zero.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
9.2 912 Jogacceleration s FLOAT 5.0 0.01 1000.00 RW FVS
9.3 914 Jogdeceleration s FLOAT 5.0 0.01 1000.00 RW FVS
Setting of the acceleration/deceleration ramp time (in seconds) used during Jog operation.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
9.4 916 Jogcmd+src LINK 16 6000 0 16384 RW FVS
Selection of the origin (source) of the Jog+ function enabling signal. When this command is enabled it generates a
Jog Mode reference with a sign matching the value entered for the Jogsetpointvalue parameter. The signal to be
associated with this function can be selected from the “L_DIGSEL2” selection list.
Note ! The Run command has priority over the Jog+ command.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
9.5 918 Jogcmd-src LINK 16 6000 0 16384 RW FVS
Selection of the origin (source) of the Jog- function enabling signal. When this command is enabled the Jog Mode
reference sign is inverted with respect to the value entered in the Jogsetpointvalue parameter. The signal to be
associated with this function can be selected from the “L_DIGSEL2” selection list.
Note ! The Run command has priority over the Jog-command.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
9.6 920 Jogoutputmon rpm INT16 16/32 0 0 0 ER FVS
The speed reference used by the Jog command is displayed.