EasyManua.ls Logo

Gentner VRC2000 - Page 50

Default Icon
140 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 44 VRC2000 Installation and Operations Manual
Technical or Setup Assistance
Telephone: 800.945.7730 (USA) or 801.975.7200 (worldwide) Worldwide Web @ http://www.gentner.com
You enter
“5”
The VRC2000 will respond with a double [BEEP].
This metering channel is now programmed to read in linear values (as a
result of entering “5”). The VRC2000 will say [I] to indicate the indirect
configuration; entering a “4” will configure this metering channel for
indirect readings. The VRC2000 will say [P] to indicate the power
configuration; entering a “7” will configure the metering channel for power
readings.
The VRC2000 will say
• RANGE FOR METERING CHANNEL ONE IS ... {ZERO TO PLUS TEN}
You enter
“#”
The VRC2000 will respond with a double [BEEP].
This metering channel is now programmed to read in a range of 0–10Vdc.
Any metering channel can be programmed to read in a range of 0–10Vdc, or
from -5–5Vdc. Enter a “*” to program this metering channel to read from
-5–5Vdc; enter a “#” to read from 0–10Vdc.
The VRC2000 will say
• CALIBRATION CONSTANT FOR METERING CHANNEL ONE IS ... {ONE POINT ZERO
ZERO ZERO}
You enter
“3 * 1 4 2”
The VRC2000 will respond with a double [BEEP].
This metering channel is now configured to use the value +3.142 as the
calibration constant.
Another option is to change the units identifier to make metering readings
easier to understand. To use the calibration constant and/or units identifier
to obtain actual voltage or current readings (based on a sample), refer to the
following example.
The VRC2000 will say
DEFAULT COMMAND CHANNEL FOR METERING CHANNEL ONE IS ... {DISABLED}
You enter
“1 0”
The VRC2000 will respond with a double [BEEP].
VRC2000 Setup
Continued

Table of Contents