EasyManua.ls Logo

Gentner VRC2000 - Step 2 - Metering Connections; Step 3 - Determine Status-Channel Input Range; Figure 14. VRC2000 Back-Panel Connectors; Figure 15. VRC2000 Metering-Channel Input Schematic

Default Icon
140 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VRC2000 Installation and Operations Manual Page 69
Technical or Setup Assistance
Telephone: 800.945.7730 (USA) or 801.975.7200 (worldwide) Worldwide Web @ http://www.gentner.com
Step 2 — Metering Connections
The VRC2000s 16 metering-channel inputs are arranged together in the
DB37 connector [7] labeled METERING on the units rear panel (Figure 14,
below). For electrical specifications, see Specifications (Page 90). For
pinouts, see Appendix B: Connector Pinouts (Page 98).
Figure 14. VRC2000 back-panel
connectors
Figure 15. VRC2000 metering-channel
input schematic
Each metering channel has two programmable upper tolerance limits, and
two programmable lower tolerance limits. Each metering channel can also be
calibrated in a linear numeric value proportional to input, or a power-to-
linear input conversion. Metering channels can also be programmed to read
indirect power (the multiplication of two consecutive channels, with the
result appearing in the third channel as a new calibrated value).
Figure 15 (See below.) represents a single VRC2000 metering-channel input.
Each metering-channel input is unbalanced, and is referenced to chassis
ground.
Connect the VRC2000 METERING connector to desired site equipment,
remembering that input levels for metering channels must not exceed -5–
10Vdc (voltage reading) or -5–10mA (current reading).
Step 3 — Determine Status-Channel Input Range
When the VRC2000 takes status readings, the voltage sample is broken down
into two categories, logic 1 (open) or logic 2 (closed). How the readings is
broken down is determined by the sample itself:
0–.8Vdc = Logic 0 (closed)
2–5Vdc = Logic 1 (open)
Higher DC voltage levels can be connected to a status-channel input if a
series diode is inserted to make the open range float (Figure 16, left).
To protect the status channel from power surges, connect a relay to the input
and ground (Figure 17, left). When the relay closes, input goes low.
CLOSURE-TO-GROUND NOTE:
Without a closure to ground, each status-channel input will read open (logic 1).
Figure 17. Status-channel surge
protection
Figure 16. VRC2000 status-channel
input with series diode inserted

Table of Contents