Page 46 VRC2000 Installation and Operations Manual
Technical or Setup Assistance
Telephone: 800.945.7730 (USA) or 801.975.7200 (worldwide) Worldwide Web @ http://www.gentner.com
You enter
“2 * 3 4 6”
The VRC2000 will respond with a double [BEEP].
The lowest tolerance limit has now been programmed with a value of 2.346.
This is now the lowest value the metering channel will permit.
All tolerance limits must be set according to the result of the voltage or
current sample for each metering channel and the associated calibration
constant.
The VRC2000 will say
COMMAND CHANNEL NUMBER FOR SECOND LOW LIMIT OF METERING CHANNEL
ONE IS ... {DISABLED}
You enter
“1 6”
The VRC2000 will respond with a double [BEEP].
Command channel 16 is now selected to automatically activate when the
second low tolerance limit is met on this metering channel. This parameter
allows the specific command channel to be automatically activated if the
second low tolerance limit on a metering channel is passed to be selected.
Also select the switch to be fired for that command channel.
When programming this parameter, enter “0 0” to disable the automatic
command-channel assignment for the metering channels second low
tolerance limit. Always use two digits to program this parameter.
When tying a command channel to a status channel (as in this example), the
VRC2000 will say
ACTIVE COMMAND CHANNEL SWITCH FOR SECOND LOW LIMIT OF METERING
CHANNEL ONE IS ...
Since each command channel has two switches, now enter a code to instruct
the VRC2000 whether to fire command channel 16s A switch or the B
switch when metering channel 1s second low limit is passed.
You enter
“#”
The VRC2000 will respond with a double [BEEP].
The VRC2000 is now programmed to automatically fire command channel
16s B switch when the second low tolerance limit for metering channel 1 is
met. Entering “#” indicates the B switch; entering “*” indicates the A
switch.