EasyManua.ls Logo

GM V2H Bundle - Appendix A: Product Datasheets; Appendix B: Design Guidelines

Default Icon
96 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GM Energy V2H Bundle Installation Manual 80
APPENDIX A: PRODUCT DATASHEETS
Please refer to GM Energy website for product data sheets at https://gmenergy.gm.com/for-home/resources-and-support
APPENDIX B: DESIGN GUIDELINES
o
Determine Charger breaker size:
If available, use Green Button data/usage data to size Charger breaker as large as possible without triggering a main
panel upgrade (MPU).
Otherwise, perform traditional NEC load calculations and determine largest breaker possible without triggering MPU.
o
Show DIP switch setting on installation notes corresponding with selected size (see Section 4.2).
o
Minimum practical Charger breaker size = 40 A.
o
Determine loads being backed up:
Prioritize single-pole circuits, lighting, and plugs.
No individual load greater than 40 A (based on Inverter rating).
No individual load with an LRA (Locked Rotor Amperage) than 62 A.
o
Soft starters may be installed to reduce startup current of inductive loads (such as air conditioner) although
performance is not guaranteed.
Follow guidance for interior located subpanels having potentially disqualifying loads:
If they can be easily routed out via exterior (such as an AC unit with an exterior disconnect), add notes to enable
inclusion in scope of work.
Otherwise, subpanel is disqualified for backup.
o
Add load calculations to PVE-2:
If using traditional load calculation, include:
Whole-home load calculation.
Hub load calculation.
If using green button data/usage data, only include that calculation justifying Charger breaker size, and Hub load
calculation.
o
Choose appropriate Hub interconnection method based on existing panel limitations, and load calculation of circuits being
relocated:
Branch breaker
Lug kit
Hub as Main Service Entrance
May require using non-backup panel, limited to 110 A.
Use appropriate resources to determine max. branch breaker/lug kit compatibility.
NEC 705 rules apply: 120% rule, sum of breakers, or PCS to protect MSP busbar.
Prioritize using PCS whenever possible and avoid relocating non-backup loads out of MSP.
o
Hub backup panel limited to 200 A total (125 A max. branch breaker).
Must use Eaton BR or BQ type breakers.
Backup panel in Hub contains 12 single pole breaker spots. One dual pole 60A breaker is pre-installed for Inverter.
The pre-installed 60A breaker in the Hub must be used for the Inverter. Do not replace this breaker unless replacing
with a breaker of the same or similar model.
Ensure no single load exceeds 40A continuous rated current. Loads that cannot be powered by Inverter during an
outage should be landed on a non-backup panel.

Table of Contents

Other manuals for GM V2H Bundle

Related product manuals