EasyManua.ls Logo

GM V2H Bundle - Hub-Inverter Power Wire Connection; Grid Power Wire Connection

Default Icon
96 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GM Energy V2H Bundle Installation Manual 43
HubInverter Power Wire Connection
Use only 90°C copper wire for Inverter wiring.
1. Install 1″ conduit into the left 1″ conduit hole on the bottom of the Hub.
2. Pull the Inverter power wires from the Inverter through this conduit into the Hub.
3. Strip and tighten the AC conductors (L1, L2, N, G) according to Figure 29 callout 2 and Table 11.
Grid Power Wire Connection
Depending on your conduit strategy, attach conduit and a watertight conduit fitting to either the 2″ Grid knockout on the
bottom right OR the 2 Grid knockout on the side right (see Figure 8). Pull the Hub AC feeders (black L1, red L2, green
ground, and gray neutral/PE) wires through the conduit into either of the 2″ entries, and then strip 1.25” from each end.
Land the wires and tighten as per Figure 29 callout 4 and Table 5. Table 12 shows the wiring information for the
connections shown in Figure 31.
Terminal
Wire Gauge
(AWG)
Wire Strip Length
(in.)
Tool
Torque for Wire Size
(in-lb / N-m)
A
Grid and load main lug
6250 kcmil
1.25
5/16″
hex
275 / 31 for 3/0250
kcmil
94 / 11 for #32/0 AWG
45 / 5 for #64 AWG
B
Neutral main lug
C
Neutral and ground
lug (large)
142/0
0.55
3/16″
hex
45 / 5 for #148 AWG
110 / 12.5 for #64 AWG
150 / 17 for #32/0 AWG
D
Neutral and ground
lug (small)
144
0.55
5 mm
slotted
20 / 2.3 for #1410 AWG
25 / 2.8 for #84 AWG
Table 12

Table of Contents

Other manuals for GM V2H Bundle

Related product manuals