30
COOLING PERFORMANCE DATA
GSH130421A*
EXPANDED PERFORMANCE DATA
COOLING OPERATION
MODEL: GSH130421A* / ARUF49-00*-1* / ARUF36421A*
Outdoor Ambient Temperature
65 75 85 95 105 115
Entering Indoor Wet Bulb Temperature
IDB*Airflow 5963677159636771596367715963 67 715963677159636771
MBh 39.2 40.6 44.5 - 38.3 39.7 43.5 - 37.4 38.7 42.4 - 36.5 37.8 41.4 - 34.6 35.9 39.3 - 32.1 33.3 36.4 -
S/T 0.77 0.64 0.44 - 0.79 0.66 0.46 - 0.81 0.68 0.47 - 0.84 0.70 0.49 - 0.87 0.73 0.50 - 0.88 0.73 0.51 -
Delta T 16 14 11 - 17 14 11 - 17 14 11 - 17 14 11 - 16 14 11 - 15 13 10 -
1688 KW 2.84 2.90 2.98 - 3.05 3.11 3.20 - 3.22 3.29 3.39 - 3.38 3.45 3.56 - 3.51 3.59 3.70 - 3.63 3.70 3.82 -
AMPS 10.6 10.8 11.2 - 11.4 11.7 12.1 - 12.4 12.7 13.1 - 13.2 13.6 14.0 - 14.1 14.4 14.9 - 14.9 15.3 15.8 -
HI PR 137 148 156 - 154 166 175 - 175 188 199 - 199 215 227 - 224 241 255 - 248 267 282 -
LO PR 60 64 70 - 64 68 74 - 66 70 77 - 70 74 81 - 73 78 85 - 75 80 88 -
MBh 38.1 39.4 43.2 - 37.2 38.5 42.2 - 36.3 37.6 41.2 - 35.4 36.7 40.2 - 33.6 34.9 38.2 - 31.2 32.3 35.4 -
S/T 0.73 0.61 0.42 - 0.76 0.63 0.44 - 0.78 0.65 0.45 - 0.80 0.67 0.46 - 0.83 0.69 0.48 - 0.84 0.70 0.49 -
Delta T 17 15 11 - 17 15 11 - 17 15 11 - 17 15 11 - 17 15 11 - 16 14 11 -
70 1500 KW 2.82 2.88 2.96 - 3.02 3.08 3.17 - 3.20 3.26 3.36 - 3.35 3.42 3.53 - 3.49 3.56 3.67 - 3.60 3.68 3.79 -
AMPS 10.5 10.7 11.1 - 11.3 11.6 11.9 - 12.3 12.6 13.0 - 13.1 13.4 13.9 - 13.9 14.3 14.8 - 14.8 15.1 15.6 -
HI PR 136 146 154 - 152 164 173 - 173 187 197 - 197 212 224 - 222 239 252 - 245 264 279 -
LO PR 60 63 69 - 63 67 73 - 66 70 76 - 69 73 80 - 72 77 84 - 75 79 87 -
MBh 35.1 36.4 39.9 - 34.3 35.6 39.0 - 33.5 34.7 38.0 - 32.7 33.9 37.1 - 31.0 32.2 35.2 - 28.8 29.8 32.7 -
S/T 0.70 0.59 0.41 - 0.73 0.61 0.42 - 0.75 0.63 0.43 - 0.77 0.65 0.45 - 0.80 0.67 0.46 - 0.81 0.68 0.47 -
Delta T 17 15 11 - 18 15 12 - 18 15 12 - 18 15 12 - 17 15 11 - 16 14 11 -
1313 KW 2.76 2.82 2.90 - 2.96 3.01 3.10 - 3.13 3.19 3.28 - 3.28 3.34 3.45 - 3.40 3.47 3.58 - 3.51 3.59 3.70 -
AMPS 10.2 10.4 10.8 - 11.0 11.3 11.6 - 11.9 12.2 12.6 - 12.7 13.1 13.5 - 13.6 13.9 14.4 - 14.4 14.7 15.2 -
HI PR 132 142 150 - 148 159 168 - 168 181 191 - 191 206 218 - 215 232 245 - 238 256 270 -
LO PR 58 62 67 - 61 65 71 - 64 68 74 - 67 71 78 - 70 74 81 - 72 77 84 -
MBh 39.9 41.0 44.4 47.7 38.9 40.1 43.4 46.6 38.0 39.1 42.4 45.5 37.1 38.2 41.3 44.4 35.2 36.3 39.3 42.1 32.6 33.6 36.4 39.0
S/T 0.870.780.590.380.900.810.610.390.930.830.630.400.950.85 0.65 0.42 0.99 0.89 0.67 0.43 1.00 0.89 0.68 0.44
Delta T1917141019181410191814101918 15 10 19 18 14 10 18 16 13 9
1688 KW 2.87 2.92 3.01 3.10 3.07 3.13 3.22 3.32 3.25 3.31 3.41 3.52 3.41 3.48 3.58 3.70 3.54 3.62 3.73 3.85 3.66 3.73 3.85 3.97
AMPS 10.7 10.9 11.3 11.7 11.5 11.8 12.2 12.6 12.5 12.8 13.2 13.7 13.4 13.7 14.1 14.7 14.2 14.6 15.0 15.6 15.1 15.4 15.9 16.5
HI PR 139 149 157 164 155 167 177 184 177 190 201 210 201 217 229 239 227 244 257 269 250 269 285 297
LO PR 61 65 71 75 64 68 75 80 67 71 78 83 70 75 82 87 74 78 85 91 76 81 88 94
MBh 38.7 39.8 43.1 46.3 37.8 38.9 42.1 45.2 36.9 38.0 41.1 44.1 36.0 37.1 40.1 43.1 34.2 35.2 38.1 40.9 31.7 32.6 35.3 37.9
S/T 0.830.740.560.360.860.770.580.370.880.790.600.380.91
0.81
0.62 0.40 0.95 0.85 0.64 0.41 0.95 0.85 0.65 0.42
Delta T2018151020181510201815102019 15 10 20 18 15 10 19 17 14 10
75 1500 KW 2.84 2.90 2.98 3.07 3.05 3.11 3.20 3.30 3.22 3.29 3.39 3.49 3.38 3.45 3.56 3.67 3.51 3.59 3.70 3.82 3.63 3.70 3.82 3.94
AMPS 10.6 10.8 11.2 11.6 11.4 11.7 12.1 12.5 12.4 12.7 13.1 13.6 13.2
13.6
14.0 14.5 14.1 14.4 14.9 15.5 14.9 15.3 15.8 16.4
HI PR 137 148 156 163 154 166 175 182 175 188 199 208 199 215 227 236 224 241 255 266 248 267 282 294
LO PR 60 64 70 75 64 68 74 79 66 70 77 82 70 74 81 86 73 78 85 90 75 80 88 93
MBh 35.7 36.8 39.8 42.7 34.9 35.9 38.9 41.7 34.1 35.1 38.0 40.7 33.2 34.2 37.0 39.7 31.6 32.5 35.2 37.8 29.2 30.1 32.6 35.0
S/T 0.800.720.540.350.830.740.560.360.850.760.580.370.88
0.79
0.59 0.38 0.91 0.82 0.62 0.40 0.92 0.82 0.62 0.40
Delta T2018151020191511201915112019 15 11 20 19 15 10 19 17 14 10
1313 KW 2.78 2.84 2.92 3.00 2.98 3.04 3.13 3.22 3.15 3.21 3.31 3.41 3.30 3.37 3.47 3.58 3.43 3.50 3.61 3.72 3.54 3.62 3.73 3.85
AMPS 10.3 10.5 10.9 11.3 11.1 11.4 11.7 12.2 12.0 12.3 12.7 13.2 12.9
13.2
13.6 14.1 13.7 14.0 14.5 15.0 14.5 14.9 15.4 15.9
HI PR 133 143 151 158 149 161 170 177 170 183 193 201 193 208 220 229 218 234 247 258 240 259 273 285
LO PR 58 62 68 72 62 66 72 76 64 68 75 79 67 72 78 83 71 75 82 87 73 78 85 90
Shaded area is ACCA (TVA) conditions IDB: Entering Indoor Dry Bulb Temperature KW=Total system power AMPS=outdoor unit amps (comp.+fan)
High and low pressures are measured at the liquid and suction service valves.