COOLING PERFORMANCE DATA
GSH130604A*
EXPANDED PERFORMANCE DATA
COOLING OPERATION
MODEL: GSH13060-4A* / ARUF61-00*-1* / ARUF48601A* Design Subcooling 9 ±3 °F @ the liquid service valve, AHRI 95 test conditions
Outdoor Ambient Temperature
65 75 85 95 105 115
Entering Indoor Wet Bulb Temperature
IDB Airflow 59 63 67 71 59 6
67 71 59 6
6
71 59 63 6
71 59 63 67 71 59 63 67 71
MBh 54.4 56.4 61.8 - 53.1 55.1 60.3 - 51.9 53.7 58.9 - 50.6 52.4 57.5 - 48.1 49.8 54.6 - 44.5 46.1 50.6 -
S/T 0.72 0.60 0.42 - 0.75 0.63 0.43 - 0.77 0.64 0.44 - 0.79 0.66 0.46 - 0.82 0.69 0.48 - 0.83 0.69 0.48 -
Delta T 18 15 12 - 18 16 12 - 18 16 12 - 18 16 12 - 18 16 12 - 17 15 11 -
2025 KW 3.98 4.06 4.18 - 4.26 4.35 4.48 - 4.52 4.61 4.75 - 4.74 4.84 4.99 - 4.93 5.04 5.19 - 5.09 5.20 5.37 -
AMPS 3.2 3.2 3.3 - 3.3 3.3 3.3 - 3.3 3.3 3.3 - 3.3 3.4 3.4 - 3.4 3.4 3.4 - 3.4 3.4 3.5 -
HI PR 152 163 173 - 170 183 194 - 194 209 220 - 221 238 251 - 248 267 282 - 274 295 312 -
LO PR 59 62 68 - 62 66 72 - 64 68 75 - 68 72 78 - 71 75 82 - 73 78 85 -
MBh 52.8 54.7 60.0 - 51.6 53.5 58.6 - 50.3 52.2 57.2 - 49.1 50.9 55.8 - 46.7 48.4 53.0 - 43.2 44.8 49.1 -
S/T 0.69 0.58 0.40 - 0.71 0.60 0.41 - 0.73 0.61 0.42 - 0.76 0.63 0.44 - 0.79 0.66 0.45 - 0.79 0.66 0.46 -
Delta T 19 16 12 - 19 16 12 - 19 16 12 - 19 16 12 - 19 16 12 - 17 15 11 -
70 1800 KW 3.95 4.03 4.14 - 4.23 4.32 4.45 - 4.48 4.57 4.72 - 4.70 4.80 4.95 - 4.89 5.00 5.15 - 5.05 5.16 5.33 -
AMPS 3.2 3.2 3.2 - 3.3 3.3 3.3 - 3.3 3.3 3.3 - 3.3 3.4 3.4 - 3.4 3.4 3.4 - 3.4 3.4 3.5 -
HI PR 150 162 171 - 169 182 192 - 192 206 218 - 219 235 248 - 246 265 279 - 272 292 309 -
LO PR 58 62 67 - 61 65 71 - 64 68 74 - 67 71 78 - 70 75 81 - 73 77 84 -
MBh 48.7 50.5 55.3 - 47.6 49.3 54.1 - 46.5 48.2 52.8 - 45.3 47.0 51.5 - 43.1 44.6 48.9 - 39.9 41.4 45.3 -
S/T 0.67 0.56 0.38 - 0.69 0.58 0.40 - 0.71 0.59 0.41 - 0.73 0.61 0.42 - 0.76 0.63 0.44 - 0.76 0.64 0.44 -
Delta T 19 16 12 - 19 17 13 - 19 17 13 - 19 17 13 - 19 16 13 - 18 15 12 -
1575 KW 3.86 3.94 4.05 - 4.14 4.22 4.34 - 4.38 4.47 4.60 - 4.59 4.69 4.83 - 4.78 4.88 5.03 - 4.93 5.04 5.20 -
AMPS 3.2 3.2 3.2 - 3.2 3.3 3.3 - 3.3 3.3 3.3 - 3.3 3.3 3.4 - 3.4 3.4 3.4 - 3.4 3.4 3.4 -
HI PR 146 157 166 - 164 176 186 - 186 200 211 - 212 228 241 - 238 257 271 - 263 284 299 -
LO PR 56 60 65 - 59 63 69 - 62 66 72 - 65 69 75 - 68 72 79 - 70 75 82 -
MBh 55.31 56.94 61.64 66.15 54.02 55.62 60.20 64.61 52.73 54.30 58.77 63.08 51.45 52.97 57.34 61.54 48.88 50.32 54.47 58.46 45.27 46.61 50.46 54.15
S/T 0.82 0.74 0.56 0.36 0.85 0.76 0.58 0.37 0.87 0.78 0.59 0.38 0.90 0.81 0.61 0.39 0.94 0.84 0.63 0.41 0.94 0.84 0.64 0.41
Delta T21191611211916112119161121 19 16 112119161119181510
2025 KW 4.01 4.09 4.21 4.34 4.30 4.38 4.52 4.66 4.55 4.65 4.79 4.94 4.78 4.88 5.03 5.19 4.97 5.08 5.24 5.41 5.14 5.25 5.41 5.59
AMPS 3.2 3.2 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.5 3.4 3.5 3.5 3.5
HI PR 153 165 174 182 172 185 196 204 196 211 222 232 223 240 253 264 251 270 285 297 277 298 315 328
LO PR 59 63 69 73 63 67 73 77 65 69 75 80 68 73 79 84 72 76 83 88 74 79 86 92
MBh 53.755.359.864.252.454.058.462.751.252.757.161.250.0
51.4
55.7 59.7 47.5 48.9 52.9 56.8 44.0 45.3 49.0 52.6
S/T 0.78 0.70 0.53 0.34 0.81 0.73 0.55 0.35 0.83 0.75 0.56 0.36 0.86
0.77
0.58 0.37 0.89 0.80 0.60 0.39 0.90 0.81 0.61 0.39
Delta T22201611222016112220161122
20
17 11 22 20 16 11 20 19 15 11
75 1800 KW 3.98 4.06 4.18 4.30 4.26 4.35 4.48 4.62 4.52 4.61 4.75 4.90 4.74
4.84
4.99 5.15 4.93 5.04 5.19 5.36 5.10 5.20 5.37 5.54
AMPS 3.2 3.2 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.4 3.3
3.4
3.4 3.4 3.4 3.4 3.4 3.5 3.4 3.4 3.5 3.5
HI PR 152 163 173 180 170 183 194 202 194 209 220 230 221
238
251 262 248 267 282 294 274 295 312 325
LO PR 59 62 68 72 62 66 72 77 64 68 75 80 68
72
79 84 71 75 82 88 73 78 85 91
MBh 49.651.055.259.348.449.853.957.947.348.752.756.546.147.47 51.4 55.143.845.148.852.440.641.845.248.5
S/T 0.76 0.68 0.51 0.33 0.78 0.70 0.53 0.34 0.80 0.72 0.54 0.35 0.83 0.74 0.56 0.36 0.86 0.77 0.58 0.37 0.87 0.78 0.59 0.38
Delta T22201611222017122220171222 21 17 122220171121191611
1575 KW 3.89 3.97 4.08 4.20 4.17 4.25 4.38 4.51 4.41 4.50 4.64 4.79 4.63 4.73 4.87 5.03 4.81 4.92 5.07 5.23 4.97 5.08 5.24 5.41
AMPS 3.2 3.2 3.2 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.5
HI PR 147 159 167 175 165 178 188 196 188 202 214 223 214 230 243 254 241 259 274 286 266 286 302 315
LO PR 57 60 66 70 60 64 70 74 62 66 72 77 66 70 76 81 69 73 80 85 71 76 83 88
Shaded area is ACCA (TVA) conditions IDB: Entering Indoor Dry Bulb Temperature KW=Total system power AMPS=outdoor unit amps (comp.+fan )
High and low pressures are measured at the liquid and suction service valves.