SmartFOAM
START-UP CHECKLIST
Before energizing the apparatus and Hale SmartFOAM system for the first time, make sure the following items are
checked:
ELECTRICAL
Tank level sensor wires connected to distribution box and sealed from moisture.
Tank level sensor functions properly.
Control cable connection at distribution box correct and tight.
Flow sensor cable properly connected.
All cables and wires are secured and protected from damage during operation.
Control and flow sensor cables properly folded and secured; radio antennas, power lines and equipment away
from cables.
Foam pump and motor assembly properly grounded using flat ground strap.
Correct voltage provided. Direct current, negative (–) ground.
Adequate current available (see Table 2: Specifications 1.7 and 2.1, Table 3: Specifications 3.3 and 5.0,
and Table 4: Specifications 6.5).
Main power direct to battery, battery switch or properly sized solenoid without primer or other accessories tied in.
Correct motor voltage (provided by the converter, 24V) when installing the 501-4480-06-0 system on a 12V appa-
ratus. Converter output current, negative (–) ground.
Motor voltage (provided by the converter, 24V, when installing the 501-4480-06-0 system on a 12V apparatus)
NOT connected anywhere other than motor.
Primary electrical and ground connections tight and protected from corrosion with silicone sealant.
Splices in wires sealed from moisture using adhesive filled heat shrink tubing.
LIQUID
Flow sensor mounted with flow arrow in the correct direction for water flow.
Check valves are properly mounted in water and foam concentrate lines.
Strainer mounted for proper concentrate flow direction in foam tank to pump hose.
Foam tank to foam pump valve is in place and open.
Check valve/injector fitting lines are proper size and connections are tight.
Bypass valve is properly mounted and oriented for direction of concentrate flow.
Foam concentrate gravity feeds to foam pump from foam concentrate tank.
All hoses free of kinks and sharp bends.
No sharp bends that can trap air exist in system.
Flush water connections correct and tight.
Discharge piping hydro tested in accordance with NFPA/UL requirements.
Bypass valve handle is in the INJECT position.
FOAM PUMP
Foam pump and motor assembly mounted in horizontal position with base plate down.
Foam pump and motor assembly properly secured using proper mounting hardware.
Foam pump suction and discharge hoses connected to proper ports.
Foam pump suction and discharge hose fittings tight.