6 Using the heating system – Structure of the menus
144
20 - OIL BURNER
21 - COMBI HEATING PUMP
19-07 Prog. 2 DH1
Mo Tu We Th Fr Sa Su
On 00:00 On 00:00
Off 24:00 Off 00:00
District heating enable times
Time block 2: Various enable times can be defined for the
individual days of the week.
No. Display Description
Table 6/15 - System level / 19 - District heating
No. Display Description
20-01 Oil burner
Oil-fired boiler
Minimum
( 40) 40°
Minimum temperature of the oil-fired boiler
Set the minimum temperature of the oil-fired boiler.
(10 - 100 °C)
20-02 Oil burner
Oil-fired boiler
Maximum
( 70) 70°
Maximum temperature of the oil-fired boiler
Set the maximum temperature of the oil-fired boiler.
(10 - 100 °C)
20-03 Oil burner
Oil-fired boiler
Increase
( 5) 5°
To increase the temperature of the oil-fired boiler
Set an increase in temperature above the set value for
the oil-fired boiler.
(10 - 100 °C)
20-04 Oil burner
Oil-fired boiler hys-
teresis
( 5) 5°
Hysteresis of the oil-fired boiler
Set the difference between the switching on and swit-
ching off temperatures for the oil-fired boiler.
(10 - 100 °C)
20-05 Oil burner
Oil-fired boiler enab-
ling time
(30) 30 m
Enable time for the oil-fired boiler
The oil-fired boiler is activated if the highest load enable
temperature is not met within the preset time. (0 - 360 m)
Table 6/16 - System level / 20 - Oil-fired boiler
No. Display Description
21-01 Acc + DHW pump
Enabling temperature
Combi Acc+DWH pump
( 50) 50°
Enable temperature for the heating pump
If the preset temperature is not met, the combination
accumulator can be heated by the oil-fired boiler.
(20 - 100 °C)
Table 6/17 - System level / 21 - Combi heating pump