8 Troubleshooting – Possible faults
172
F024 Temp. acc. bot-
tom open circuit
Sensor is faulty
Open circuit in sensor cable
Sensor not connected
Connect sensor
Replace cable
Check terminal (check plug
for secure fit)
Exchange the faulty sensor
(plug on the I/O circuit board)
with a different sensor
If a different fault appears, the
sensor should be replaced
If the same fault appears, the
I/O circuit board should be
replaced
F025 Checking the
lambda
sensor
Lambda sensor faulty
Open circuit in the line
Fuse F4 (on I/O circuit board)
is faulty
Check lambda sensor, replace
if necessary
Check line and plug
Replace fuse
F026 The lambda
Sensor is faulty
Lambda sensor is faulty or
heavily soiled
Clean lambda sensor, then
recalibrate (parameter h-38)
Replace sensor if necessary
F027 Check sum error,
parameters reset
to defaults
Fault in the control EPROM,
all parameters will be reset to
factory defaults
Check all settings and adjust
current values.
F028 Safety circuit
Emergency Stop
Emergency Stop activated Unlock emergency stop
Acknowledge fault with main
switch off/on
F029 Safety circuit
Low on water
Check water pressure Unlock insufficient water
cutout
Acknowledge fault with main
switch off/on
Check plug on circuit board
22 /23
F032 Cleaning system
limit switch,
top
Cleaning function blocked
Faulty limit switch
Check cleaning system
Have limit switch checked by
a qualified electrician
F035 HC module 0
not connected
Power supply has failed
Bus cable is not connected
Bus cable is fitted the wrong
way around
Check the power supply
Check connection of bus
cable
F036 Software not
compat. with
this hardware
Software is not compatible
with this hardware
Use a new software
Notify HDG customer service
F040 Supply temp. HC1
open circuit
Sensor not connected
Sensor is faulty
Have the fault fixed by a qua-
lified electrician
No. Fault Cause Remedy
Table 8/1 - Faults