31 – 596 HEIDENHAIN Service Manual iTNC 530 HSCI
MP2220.x Monitoring functions
Format: %xxxxxxxxxxxxxxxx
Input: Bit 0 – Monitoring the reference mark
0: Monitoring active
1: Monitoring inactive
Bit 1 – Monitoring the direction of rotation
0: Monitoring active
1: Monitoring inactive
Bit 2 – Power limit of spindle with ERR.IZ.GR
(only for HEIDENHAIN
inverters, except UE 2xx)
0: Power limit active
1: Power limit inactive
(All HEIDENHAIN inverters except UE 2xx)
Bit 3 – Switching off the controller when the motor brakes are activated
0: Suppress oscillations
1: Oscillations are allowed
PLC
RUN
Bit 4 – Monitoring for excessive temperature
0: Active
1: Inactive
Bit 5 – Monitoring for insufficient temperature
0: Active
1: Inactive
Bit 6 – Reserved
Bit 7 – Monitoring of encoder input frequency
0: Active
1: Inactive
Bit 8 – Adjust mechanical offset by gradually increasing the k
V
factor
0: Active
1: Inactive
Bits 9 to 15 – Reserved
MP2221.x Bit 7 – Switch-on time of the drive
Input: 0: Reduction of the switch-on time is active
1: Reduction of the switch-on time is not active
Bit 10 – Handling of linear and synchronous motors to attain higher milling power with AFC
Input: 0: Handling for attaining higher milling power is active
1: Handling for attaining higher milling power is not active
PLC
RUN
MP2222.x Reserved
MP2223.x Reserved
MP2230.x Multiplier for motor standstill current during test of motor brake
Input: 0.1 to 30.0 [⋅ motor standstill current]
0: No test of motor brakes, or motor without brake
MP2232.x Maximum permissible path during test of motor brakes
Input: 0 to 10.0000 [mm] or [°]
MP2250.x Determining the field angle without motor motion
Input: 0: Same as input value 2
1: Reserved
2: Method 2 (brakes applied)
3: Method 3 (same as Method 2, but motor brake is not applied)
4: Method 4 (if there is a lot of noise in the encoder signals)
PLC
RUN
MP2252.x Reserved
Input: Enter 0
PLC
RUN