Forkli Filter
Enable these funcons if there is forkli in the scene, or it may cause false alarm. The lter
level can be adjusted.
Check Display Filtering Status, and an OSD will be displayed when the funcon is enabled.
Set Filtering Temperature, e.g., set the ltering temperature as 300 °C and forklis can be
ltered only when their temperature is lower than 300 °C. The funcon varies according to
dierent camera models.
Click Restart to restart algorithm library of forkli lter.
Note
Forkli Filter is mutually exclusive with VCA, Ship Detecon and Fire and Smoke Detecon.
4.
Click Save.
3.3.2 Set Normal Mode
This funcon is used to measure the temperature of the whole scene and alarm.
Steps
1.
Go to Conguraon → Temperature Measurement → Basic Sengs , and check Enable
Temperature Measurement.
2.
Refer to
Set Thermography Parameters to set the parameters.
3.
Go to
Conguraon → Temperature Measurement → Advanced Sengs , and select Normal.
4.
Congure the parameters of normal mode.
Emissivity
Set the emissivity of your target. The emissivity of each object is
dierent.
Distance
The distance between the target and the device.
Pre-Alarm Threshold
When the temperature of target exceeds the pre-alarm threshold, and this status keeps more
than Filtering Time, it triggers pre-alarm.
Alarm Threshold
When the temperature of target exceeds the alarm threshold, and this status keeps more
than Filtering Time, it triggers alarm.
Pre-Alarm Output and Alarm Output
Check Pre-Alarm Output and Alarm Output to link the pre-alarm or alarm with the
connected alarm device.
5.
Refer to
Set Arming Schedule for seng scheduled me. Refer to Linkage Method Sengs for
seng linkage method.
6.
Click Save.
The maximum and minimum temperature will be displayed on the live view.
Thermal & Opcal Bi-spectrum PTZ Network Camera User Manual
9