110
Troubleshooting
Cause of
Stoppage
(Alarm Code or
Stoppage Code)
Contents
Indication of Alarm Code History
Time *Alarm
Alarm Code
Alarm Code
or Stoppage
Code
O.U.
Unit No.
Comp.
No.
Fan No.
48
Activation of inverter overcurrent protection
device
Accumulated Time AC. iTC
d1-17 Accumulated Time d1. iTC
51
Abnormality of inverter current sensor
Accumulated Time AC. iTC
d1-17 Accumulated Time d1. iTC
53
Inverter error signal detection
Accumulated Time AC. iTC
d1-17 Accumulated Time d1. iTC
54
Abnormality of inverter n temperature
Accumulated Time AC. iTC
d1-17 Accumulated Time d1. iTC
55
Inverter failure
Accumulated Time AC. iTC
d1-18 Accumulated Time d1. iTC
57 Activation of fan controller protection device Accumulated Time AC. FTC
5A Abnormality of Fan Controller Fin Temperature Accumulated Time AC. FTC
5b Activation of Overcurrent Protection Accumulated Time AC. FTC
5c Abnormality of Fan Controller Sensor Accumulated Time AC. FTC
EE Compressor protection alarm Accumulated Time AC. --
A6
Abnormality of PCB cooling module
temperature
Accumulated Time AC. --
d1-42 Accumulated Time d1. --
b5
Incorrect setting of indoor unit connection
number
Accumulated Time AC. --
d1-05 Instantaneous power failure Accumulated Time di. --
d1-18 Abnormality of inverter and other Accumulated Time di. iTC
d1-26 Abnormality of high pressure decrease Accumulated Time di. --
d1-32
Retry stoppage by indoor unit auto address
setting
Accumulated Time di. --
Control
Information
Micro-computer reset by abnormality of
inverter transmission
Accumulated Time Ci. 1
Micro-computer reset by abnormality of fan
controller transmission
Accumulated Time Ci. 2
Micro-computer reset by abnormality of indoor
unit transmission
Accumulated Time Ci. 3
Micro-computer reset by abnormality
transmitting between outdoor unit and outdoor
unit
Accumulated Time Ci. 4
Micro-computer reset for abnormality of
control state
Accumulated Time Ci. 6
*(Details of Alarm) iTC: Inverter Stoppage Code
AC.: Alarm FTC: Fan Controller Stoppage Code
d1.: Retry
Ci.: Control Information
(2) Deletion of Alarm Code History
Press PSW1 and PSW3 for 5 seconds to clear the alarm code history while the history data is displayed. (All history can
be deleted.)
PSW4(▼) PSW2(▲)
PSW4(▼) PSW2(▲)
PSW2(▲)
PSW4(▼) PSW2(▲)
PSW4(▼)
PSW4(▼)
PSW2(▲)
PSW3( )
PSW5( )
In order to delete all the history,
press PSW1 and PSW3 ( )
for 5 seconds
while history is displayed.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hisense AVWT-192FFFH and is the answer not in the manual?

Hisense AVWT-192FFFH Specifications

General IconGeneral
BrandHisense
ModelAVWT-192FFFH
CategoryAir Conditioner
LanguageEnglish

Related product manuals