EasyManuals Logo

Hisense AVWT-192FFFH User Manual

Hisense AVWT-192FFFH
317 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #3 background imageLoading...
Page #3 background image
I
Dear user:
Thank you for choosing and using our products. For your better understanding and use of this product, be sure to read and
comply with the following related matters before use
.
IMPORTANT NOTICE
Signal words (danger, warning and caution) are used to identify levels of hazard seriousness. Denitions for identifying hazard
levels are provided below with their respective signal words:
: A hazardous situation which, if not avoided, will result in death or serious injury.
: A hazardous situation which, if not avoided, could result in death or serious injury.
: Used with the safety alert symbol, indicates a hazardous situation which, if not
avoided, could result in minor or moderate injury.
: Useful information for operation and/or maintenance.
This manual should be considered as a permanent part of the air conditioning equipment and should remain with the air
conditioning equipment.
This manual gives a common description and information for this air conditioner which you operate as well for other
models. HISENSE pursues a policy of continuing improvement in design and performance of products. The right is
therefore reserved to vary specications without notice.
HISENSE cannot anticipate every possible circumstance that might involve a potential hazard. This air conditioner is
designed for standard air conditioning only. Do not use this heat recovery air conditioner for other purposes such as
drying clothes, refrigerating foods or for any other cooling or heating process. Do not install the unit in the following
places. It may cause a re, deformation, corrosion or failure.
* Places where oil (including machinery oil) sprays * Places where a lot of sulde gas drifts such as in hot
spring.
* Places where inammable gas may generate or ow. * Places where strong salty wind blows such as coast
regions, or places with high acidity or alkalinity.
Do not install the unit in the place where silicon gas drifts. If the silicon gas attaches to the surface of heat exchanger,
the n surface repels water. As a result, drain water splashes outside of the drain pan and splashed water runs inside of
electrical box. In the end, water leakage or electrical devices failure may occur.
Do not install the unit in the place where the breeze directly catches the animals and plants. It could adversely a󰀨ect the
animals and plants.
Installation and service engineering must comply with local standards, laws and regulations.
As the “public inaccessible appliances”, the indoor units are required to be installed at a height of no lower than 2.5m.
The installation of the air conditioner can only be carried out by dealer or professional, and self installation by user may
cause water leakage, electric shock or a re.
If you have any questions, contact your dealer or designated service center of HISENSE.
To prevent the environment, please do not discard the product at will, and HISENSE can provide recycling services
in accordance with the relevant provisions of the country and provide replaceable parts in accordance with national
standard requirements.
This air conditioner has been designed for the following temperatures. Operate the air conditioner within this range
Temperature °F(°C)
DX Indoor Unit Maximum Minimum Water Module Maximum Minimum
Cooling
Operation
Indoor
°F DB/°F WB
(°C DB/°C WB)
89/73
(32/23)
69/59
(21/15)
Cooling
Operation
Water Inlet °F (°C )
77
(25)
50
(10)
Outdoor
°F DB
(°C DB)
126
(52)*
14
(-10)
Outdoor
°F DB
(°C DB)
118
(48)*
50
(10)
Heating
Operation
Indoor
°F DB
(°C DB)
80
(27)
59
(15)
Heating
Operation
Water Inlet °F(°C)
130
(54)
50
(10)
Outdoor
°F WB
(°C WB)
62
(16.5)
-13
(-25)**
Outdoor
110°F DB
(43°C DB)
-13°F WB
(-25°C WB) **
DB:Dry Bulb, WB: Wet Bulb
NOTES:
(*) 118°F(48°C) DB ~ 126°F(52°C) DB, Operation Control Range
(**) -4°F(-20°C) WB ~ -13°F(-25°C) WB, Operation Control Range

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hisense AVWT-192FFFH and is the answer not in the manual?

Hisense AVWT-192FFFH Specifications

General IconGeneral
BrandHisense
ModelAVWT-192FFFH
CategoryAir Conditioner
LanguageEnglish

Related product manuals