Field Work Instruction
5.2 Maintenance Work
(1) For Outdoor Unit and Indoor Unit
(a) Fan and Fan Motor
Lubrication - All fan motors are pre-lubricated and sealed at the factory. Therefore, no lubricating maintenance is
required.
Sound and Vibration - Inspect for abnormal sound and vibration.
Rotation - Inspect for clockwise rotation and rotating speed.
Insulation - Inspect for electrical insulation resistance.
(b) Heat Exchanger
Clogging - Inspect the heat exchanger and remove any accumulated dirt or dust from the heat exchanger at regular
intervals. As for outdoor unit, other obstacles such as growing grass and pieces of paper, which might restrict air ow,
should also be removed.
(c) Piping Connection
Leakage - Inspect for refrigerant leakage at piping connections.
(d) Cabinet
Stain and Lubrication- Inspect and remove any stain or lubrication.
Fixing Screw - Inspect and x loosened or lost screws
Insulation - Inspect and repair peeled thermal insulation material on cabinet.
(e) Electrical Equipment
Activation - Inspect for abnormal activation of the magnetic contractor, auxiliary relay, PCB and etc.
Line Condition - Pay attention to working voltage, amperage and phase balance. Inspect for faulty contact caused
by loosened terminal connections, oxidized contacts, foreign matter, and other items. Inspect for electrical insulation
resistance.
(f) Control and Protective Devices
Setting - Do not readjust the setting in the eld unless the setting is maintained at a point other than the point listed in
“Safety and Control Device Setting” of TC.
(2) For Outdoor Unit Only
(a) Compressor
Sound and Vibration - Inspect for abnormal sound and vibration.
Activation - Inspect for that the voltage drop of power supply line is within 16% at start and within 2% during operation.
(b) Reversing Valve
Activation - Inspect for any abnormal activating sound.
(c) Strainer
Clog - Inspect for that no temperature di󰀨erence between both ends.
(d) Earth Wire
Earth Line - Inspect for continuity to the earth.
(e) Crankcase Heater
Activation - The crankcase heater should be activated at least 12 hours before start-up, by switching ON the main
power supply.
(3) For Indoor Unit Only
(a) Air Filter
Cleaning - Inspect and remove any accumulated dirt or dust according to “Filter Cleaning” of manual.
(b) Drain Pan, Drain-Up Mechanism and Drain Pipe
Drain Line - Inspect and clean the condensate drain line at least twice a year.
Drain-Up Mechanism - Inspect for activation of drain-up mechanism.
(c) Float Switch
Activation - Inspect for activation of oat switch

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hisense AVWT-192FFFH and is the answer not in the manual?

Hisense AVWT-192FFFH Specifications

General IconGeneral
BrandHisense
ModelAVWT-192FFFH
CategoryAir Conditioner
LanguageEnglish

Related product manuals