53
Capacities and Selection Data
<Heating Capacity >
Correction factor for cooling capacity according to piping length. The correction factors are shown in
the following gure.
The heating capacity should be corrected according to the following
formula:
Equivalent piping length for
HCA=HC×F
HCA: actual corrected cooling capacity
HC: cooling capacity in the performance table
F: correction factor based on the equivalent piping length
one 90° elbow is 1.6ft. (0.5m).
one 180° bend is 4.9ft. (1.5m).
one branch pipe is 1.6ft. (0.5m).
AVWT-72*~456*
164(5 )
148(15)
131(4
)
115(35)
98(30)
82(25)
66(20)
49(15)
33(10)
16(5)
-16(-5)
-33(-10)
-49(-15)
-66(-20)
-82(-25)
-98(-30)
-115(-35)
-131(-40)
ft.
ft.
33 328 394 427 459 492 591
AVWT-72*~456*
Normal
Size up
558361
(
)
( )
( )
( )
( )
( )
( )
( )
(
)
(
)
(
)
(
)
(
)
(
)
(
)
(
)
(
)
(
)
295
262
230
197
131 461
98
66
525
H: vertical distance between indoor unit and outdoor unit
EL: equivalent total distance between indoor unit and outdoor unit
(equivalent one-way piping length)
H>0: position of outdoor unit higher than position of indoor unit
L: actual one-way piping length between indoor unit and outdoor unit.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hisense AVWT-192FFFH and is the answer not in the manual?

Hisense AVWT-192FFFH Specifications

General IconGeneral
BrandHisense
ModelAVWT-192FFFH
CategoryAir Conditioner
LanguageEnglish

Related product manuals