67
Control System
Defrosting operation
1
No
Yes Big
Small
Heating
Defrosting
RVR2 : OFF
RVR1 : ON
RVR1 : OFF
Outdoor FAN MOF1
: OFF when defrosting
Temperature Difference
between Outdoor Temperature
and Evaporating Temperature (Te)
at Heat Exchanger
Heating Operation Time
40 Minutes or Above
No No
Yes
No
Yes
Discharge Pressure is
247psi(1.7MPa) or Above
Evaporating Temperature
(Te) at Heat Exchanger is
59°F(15°C) or Above
Yes
Defrosting Time is
9 Minutes or Above
Defrosting
Completion
Heating
Fixed Opening
Degree of Electronic
Expansion Valve
PID Control for
Super Cooling Electronic
Expansion Valve
RVR2 : ON
Compressor Operating
at Low Frequency
High Frequency
Operation
1 Minute Later
RV 2RVR
RV 1RVR
:ON
:OFF
Stop Heating Non-stop Heating
1: Defrost operation signal is transmitted to
the indoor unit during the defrost operation.
After the signal is received, “DEFROST” will
be indicated on LCD of remote control switch
and the indoor fan will be stopped.
Temperature
Conditions
in
Defrosting
Operation
50(10)
Stop Area
59(15)
41(5)
32(0)
14(-10)
14(-10) 23(-5)
5 (-15)
5(-15)
Defrosting Operation
Defrosting Operation
Start Area
Outdoor Temp.
°F(°C)
Outdoor Evaporating
Temperature °F(°C)
(Pipe)
50(10) 59(15)
-6 (-21)
41(5)
42(6)
28(-2)
22(-6)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hisense AVWT-192FFFH and is the answer not in the manual?

Hisense AVWT-192FFFH Specifications

General IconGeneral
BrandHisense
ModelAVWT-192FFFH
CategoryAir Conditioner
LanguageEnglish

Related product manuals