5. Configuration and Function of Internal Memory
5.5. PUT/GET function block use area (parameter area)
R200 Analog Input Module 2MLF-AV8A, AC8A User's Guide 105
September 2010 Honeywell
Error Code
(Decimal)
Error Contents Remark
41#
Offset value of 0~5V (0~20mA)
range is set as larger or equal than
gain value
Offset value of 0~10V range is set
as larger or equal than gain value
RUN LED flickers every
1s
Offset value of -10~10V range is
set as larger or equal than gain
value
50#
Filter constant setting range
exceeded
60#
Time average setting range
exceeded
70#
Count average setting range
exceeded
80# Analog input range setting error Applied at 2MLF-AC8A
At error code, # indicates channel where error occurs.
REFERENCE - INTERNAL
For more details on error code, refer to section Error Codes.
3. In case, two error code occurs, module saves first occurred error code and later
occurred error code is not saved
4. In case error occurs, after modifying error, use error clear request flag, restart power
to delete error code and stop LED flicker. For more details about error clear request
flag, refer to Error Clear request Flag (%UXa.b.176, a: Base No, b: Slot No.).