60 NFS2-3030 Programming Manual — P/N 52545:A 11/29/2005
Program Autoprogram Menu
Soft Keys
YES: Press this soft key to install the new point into the panel’s database.
EDIT: Press this soft key to advance to the point programming menu for the new point.
NO: Press if the point will not be installed.
Error and Discrepancy Resolution
Pressing the REVIEW soft key will bring up screens that provide the means to resolve any errors or
discrepancies found during autoprogram.
Figure 3.49 Autoprogram Confirmation Screen (Missing Point)
Display
This screen will display the SLC device address when a previously installed/programmed point
does not respond during a subsequent Autoprogram.
Soft Keys
YES: Press to delete the point information from the panel’s database.
NO: Press to leave the point information in the panel’s database.
Figure 3.50 Autoprogram Confirmation Screen (Mismatched Point)
AUTOPROGRAM CONFIRMATION
NO DEVICE FOUND AT LXXDXXX
DELETE POINT?
YES NO
BACK
AUTOPROGRAM CONFIRMATION
MISMATCHED MODULE FOUND AT L01M123
OLD:CONTROL
NEW:MONITOR
ACCEPT CHANGES?
YES NO
EDIT BACK

Table of Contents

Other manuals for Honeywell Notifier NFS2-3030

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier NFS2-3030 and is the answer not in the manual?

Honeywell Notifier NFS2-3030 Specifications

General IconGeneral
BrandHoneywell
ModelNotifier NFS2-3030
CategoryControl Panel
LanguageEnglish

Related product manuals