46 NFS2-3030 Programming Manual — P/N 52545:A 11/29/2005
Program Point Program
SILENCEABLE: This field determines whether the user can manually silence a detector’s
activated sounder/relay base. Values are as follows:
3.4.2 Module Point
Module point programming screens will display if a module point address is entered at the Point
Programming Menu (see Figure 3.24 on page 39).
Module Point Programming (1)
Figure 3.32 Module Point Programming (1) Screen
Soft Keys
MODULE TYPE: Press the soft key to toggle between CONTROL and MONITOR.
TYPE CODE LABEL: Press this soft key to scroll through the point type choices: stop at the
appropriate selection.
FLASHSCAN CODE LABEL: Press this soft key to scroll through the point type choices: stop at
the appropriate selection (Table G.4 on page 130 for codes and descriptions). Choose NONE if the
point type is not FlashScan.
POINT LABEL: Press this soft key to place the cursor at this field. Type in a 20-character
maximum point label that will appear in message formats. If no entry is made, the field will default
to the point address.
EXTENDED LABEL: Press to place the cursor at this field. Type in a 12-character maximum
extended label to further define the location or nature of the point.
MORE: Press to proceed to the next screen for more point programming.
ACCEPT: Press to save entries made on this screen.
NO Not manually silenceable
YES - RESOUND FIRE Silenceable, resound on fire alarm events Network and Local Resound
YES - RESOUND SUPERV Silenceable, resound on supervisory events Network and Local Resound
YES - NO RESOUND Silenceable, does not resound
MODULE POINT PROGRAMMING
L03M123
MODULE TYPE: MONITOR
TYPE CODE LABEL:HEAT DETECT
FLASHSCAN CODE LABEL: MONITOR MORE
POINT LABEL:
MONITOR L03M123 ACCEPT
EXTENDED LABEL:
BACK
NOTE: If the point is not installed, MODULE TYPE: , TYPE CODE LABEL:, and FLASHSCAN
CODE LABEL: must be entered before any entries can be saved using the ACCEPT key.

Table of Contents

Other manuals for Honeywell Notifier NFS2-3030

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier NFS2-3030 and is the answer not in the manual?

Honeywell Notifier NFS2-3030 Specifications

General IconGeneral
BrandHoneywell
ModelNotifier NFS2-3030
CategoryControl Panel
LanguageEnglish

Related product manuals