92 NFS2-3030 Programming Manual — P/N 52545:A 11/29/2005
Releasing Applications Abort Switches
B.3.4 AHJ Abort Switch
An AHJ (Authority Having Jurisdiction) Abort Switch has a delay timer that restores the
programmed Delay Time.
When an alarm initiates in the programmed releasing zone, the programmed Delay Time starts.
Pressing and holding the abort switch suspends the delay timer. When the abort switch is released,
the control panel restores the value of the programmed Delay Time and the delay timer counts
down. When the Delay Time expires, the control panel activates releasing zone outputs.
Figure B.7 AHJ Abort Switch
NOTE: An AHJ timer does not comply with UL Standard 864.
Delay Time: 60 seconds
Abort Switch: AHJ
Cross Zone: N
Soak Time: 0
Program selections for this releasing zone
Release the abort switch and the control
panel restores the programmed value
Delay Time (60 sec.) and counts down
Delay=60 sec.
Press and hold
the Abort
Switch (30 sec.)
When the Delay Time
expires, the control
panel activates
releasing zone outputs
30 sec.
45 sec.
60 sec.
Total time from alarm initiation to
release:
45 + 30 + 60 = 135 seconds
Alarm
0 sec.
45 sec
60 sec.
75 sec.
135 sec.

Table of Contents

Other manuals for Honeywell Notifier NFS2-3030

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier NFS2-3030 and is the answer not in the manual?

Honeywell Notifier NFS2-3030 Specifications

General IconGeneral
BrandHoneywell
ModelNotifier NFS2-3030
CategoryControl Panel
LanguageEnglish

Related product manuals