NFS2-3030 Programming Manual — P/N 52545:A 11/29/2005 49
Point Program Program
WALK TEST: This field determines if the output will activate during Walk Test. Values are ON
(the output will activate) and OFF (the output will not activate). Default: OFF.
SWITCH INHIBIT: This field determines whether a user can manually activate an output.
Values are YES (can not be activated manually) or NO (can be activated manually). Default: NO
SILENCEABLE: This field determines whether the user can manually silence an activated output.
Values are as follows:
LOCAL MODE: Press to toggle between Local Mode (ON) or no Local Mode (OFF). When there is
a communication loss between the panel and its LCM/LEMs, SLC devices that have been selected
for Local Mode participation (ON) will continue to function across all the panel’s SLCs in a limited
manner as follows: input points will activate output points of the same Type Code point type
designations. For example, SLC inputs with“fire” point types will activate SLC outputs with“fire”
point types. Refer to Appendix G.3, “Type Codes for Input Devices”, on page 127 for Type Code
point types. Default: OFF
3.4.3 General Zone
This screen displays when a general zone is chosen at the Point Program menu (see Figure 3.24 on
page 39).
NOTE: The following Type ID codes do not participate in Walk Test, and the WALK TEST soft key
will not appear when the screen displays: REL END BELL, RELEASE CKT, REL CKT ULC, REL.
FORM C, REL AUDIBLE, INST RELEASE, NONRESET CTL, TELEPHONE, and FORM-C RESET.
The FMM-1 module with SMOKE CONV, HEAT DETECT, or SMOKE DETECT does not participate
in Walk Test.
NO Not manually silenceable
YES - RESOUND FIRE Silenceable, resound on fire alarm events Network and Local Resound
YES - RESOUND SUPERV Silenceable, resound on supervisory events Network and Local Resound
YES - RESOUND SECURITY Silenceable, resound on security events Network and Local Resound
YES - RESOUND TROUBLE Silenceable, resound for trouble Local Resound
YES - NO RESOUND Silenceable, does not resound
NOTE: This soft key will not appear for modules with Type ID codes where silence is not optional.
NOTE: The panel setting LCM LOCAL MODE must be set to Yes for local mode to work at the
device level.

Table of Contents

Other manuals for Honeywell Notifier NFS2-3030

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier NFS2-3030 and is the answer not in the manual?

Honeywell Notifier NFS2-3030 Specifications

General IconGeneral
BrandHoneywell
ModelNotifier NFS2-3030
CategoryControl Panel
LanguageEnglish

Related product manuals