EasyManuals Logo

Honeywell SmartLine RMA800 User Manual

Honeywell SmartLine RMA800
144 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #105 background imageLoading...
Page #105 background image
Revision 4 Foundation Fieldbus RMA803 Remote Indicator User's Guide Page 89
FSTATE_TIME The delay time(in seconds) the MAO function block takes to set the fault
state status if an input becomes Bad and stays in that state fault state.
FSTATE_VAL1 A value transferred as input 1 to LCD Transducer Block during fault
state condition. Transition will occur if MO_OPT bit is enabled.
FSTATE_VAL2 A value transferred as input 2 to LCD Transducer Block during fault
state condition. Transition will occur if MO_OPT bit is enabled.
FSTATE_VAL3 A value transferred as input 3 to LCD Transducer Block during fault
state condition. Transition will occur if MO_OPT bit is enabled.
FSTATE_VAL4 A value transferred as input 4 to LCD Transducer Block during fault
state condition. Transition will occur if MO_OPT bit is enabled.
FSTATE_VAL5 A value transferred as input 5 to LCD Transducer Block during fault
state condition. Transition will occur if MO_OPT bit is enabled.
FSTATE_VAL6 A value transferred as input 6 to LCD Transducer Block during fault
state condition. Transition will occur if MO_OPT bit is enabled.
FSTATE_VAL7 A value transferred as input 7 to LCD Transducer Block during fault
state condition. Transition will occur if MO_OPT bit is enabled.
FSTATE_VAL8 A value transferred as input 8 to LCD Transducer Block during fault
state condition. Transition will occur if MO_OPT bit is enabled.
FSTATE_STATUS List of inputs that have transitioned to fault state status.
UPDATE_EVT Indicates event information when an event update (a change in set
values) occurs.
BLOCK_ALM Indicates alarm information when a block alarm occurs.
Attributes
Supported
Modes
The block supports the following modes:
AUTO (Automatic)
LO
O/S.
Alarm Types
Standard block alarm will be supported.
Status
Handling
The status values described in the Parameter Formal Model of Part
1 apply.
5.12 Configuring the Remote Indicator using Field Device
Manager (FDM) system
The Remote Indicator can be configured through Field Device Manager, by using DTM/DD for
R440 release and by using DTM for R430 and R410 release. For more information, refer the FDM
manual #EP-FDM-11430, #EP-FDM-11410.

Table of Contents

Other manuals for Honeywell SmartLine RMA800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell SmartLine RMA800 and is the answer not in the manual?

Honeywell SmartLine RMA800 Specifications

General IconGeneral
BrandHoneywell
ModelSmartLine RMA800
CategoryTouch Panel
LanguageEnglish

Related product manuals