EasyManua.ls Logo

Honeywell SmartLine RMA800 - Attributes; Configuring the Remote Indicator Using Field Device Manager (FDM) System

Honeywell SmartLine RMA800
144 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Revision 4 Foundation Fieldbus RMA803 Remote Indicator User's Guide Page 89
FSTATE_TIME The delay time(in seconds) the MAO function block takes to set the fault
state status if an input becomes Bad and stays in that state fault state.
FSTATE_VAL1 A value transferred as input 1 to LCD Transducer Block during fault
state condition. Transition will occur if MO_OPT bit is enabled.
FSTATE_VAL2 A value transferred as input 2 to LCD Transducer Block during fault
state condition. Transition will occur if MO_OPT bit is enabled.
FSTATE_VAL3 A value transferred as input 3 to LCD Transducer Block during fault
state condition. Transition will occur if MO_OPT bit is enabled.
FSTATE_VAL4 A value transferred as input 4 to LCD Transducer Block during fault
state condition. Transition will occur if MO_OPT bit is enabled.
FSTATE_VAL5 A value transferred as input 5 to LCD Transducer Block during fault
state condition. Transition will occur if MO_OPT bit is enabled.
FSTATE_VAL6 A value transferred as input 6 to LCD Transducer Block during fault
state condition. Transition will occur if MO_OPT bit is enabled.
FSTATE_VAL7 A value transferred as input 7 to LCD Transducer Block during fault
state condition. Transition will occur if MO_OPT bit is enabled.
FSTATE_VAL8 A value transferred as input 8 to LCD Transducer Block during fault
state condition. Transition will occur if MO_OPT bit is enabled.
FSTATE_STATUS List of inputs that have transitioned to fault state status.
UPDATE_EVT Indicates event information when an event update (a change in set
values) occurs.
BLOCK_ALM Indicates alarm information when a block alarm occurs.
Attributes
Supported
Modes
The block supports the following modes:
AUTO (Automatic)
LO
O/S.
Alarm Types
Standard block alarm will be supported.
Status
Handling
The status values described in the Parameter Formal Model of Part
1 apply.
5.12 Configuring the Remote Indicator using Field Device
Manager (FDM) system
The Remote Indicator can be configured through Field Device Manager, by using DTM/DD for
R440 release and by using DTM for R430 and R410 release. For more information, refer the FDM
manual #EP-FDM-11430, #EP-FDM-11410.

Table of Contents

Related product manuals