Revision 4  Foundation Fieldbus RMA803 Remote Indicator User's Guide  Page 101 
 
Troubleshooting the Diagnostics Transducer block 
 
Table 27: Diagnostics Transducer block 
Problem cause  Things to check  Recommended action 
Diagnostic 
Transducer block 
mode is in OOS and 
does not change to 
AUTO mode. 
Read 
MODE_BLOCK.PERMITTED 
Add AUTO mode to 
MODE_BLOCK.PERMITTED. 
Read MODE_BLOCK. 
ACTUAL of Resource block. 
If necessary, Set 
MODE_BLOCK.TARGET to 
AUTO. 
NOTE: 
If the mode is set to OOS for 
maintenance then do not change 
the mode to AUTO. 
Block alarms are not 
reported. 
Read FEATURE_SEL  Reports are not selected in 
FEATURE_SEL. If features do 
not include reports then the host 
must poll for alarms. 
Read LIM_NOTIFY  Set LIM_NOTIFY to a value 
higher than zero, but not higher 
than MAX_NOTIFY.