Page 102  Foundation Fieldbus RMA803 Remote Indicator User's Guide  Revision 4 
Troubleshooting the LCD Transducer block 
 
Table 28: LCD Transducer block 
Problem Cause  Things to check  Recommended Action 
LCD Transducer 
block mode is in OOS 
and does not change 
to AUTO mode. 
Read 
MODE_BLOCK.PERMITTED 
Add AUTO mode to 
MODE_BLOCK.PERMITTED. 
Read MODE_BLOCK. 
ACTUAL of Resource block. 
If necessary, Set MODE_BLOCK.TARGET 
to AUTO. 
NOTE 
If the mode is set to OOS for maintenance, 
then do not change the mode to AUTO. 
Writing to display 
parameters fails. 
Check for local display. 
Advanced Display is required for LCD_TB 
to work. 
If display is available, remove and 
reconnect the local display, and check if 
display powers up.  
If display is not powering up contact 
Honeywell TAC. 
NOTE 
If a user goes to menus/sub menus in the 
display, the parameter change will fail. He 
must navigate out of the menus. 
Writing to some of 
display parameter in 
SCREEN_1, 
SCREEN_2, 
SCREEN_3, 
SCREEN_4, 
SCREEN_5, 
SCREEN_6, 
SCREEN_7, 
and  
SCREEN_8  
fails. 
Check DISPLAY_TYPE. 
If there is No Display, then writing to the 
parameters fails. Parameters write is 
supported if Advanced display is connected.  
Local display shows 
Attention as title with 
some text. 
Check the 
DISPLAY_MESSAGE 
parameters. 
Remote Indicator messaging is activated; to 
clear the message executed the Clear 
Message method. For more information see 
section 5.5 
Block alarms are not 
reported. 
Read FEATURE_SEL.  Reports are not selected in 
FEATURE_SEL. If features do not include 
Reports then the host must poll for alarms. 
Read LIM_NOTIFY  Set LIM_NOTIFY to a value higher than 
zero, but not higher than MAX_NOTIFY.