Page 114  Foundation Fieldbus RMA803 Remote Indicator User's Guide  Revision 4 
8.7  Understanding write protection 
The software write lock feature can be enabled, only if the hardware write lock feature is disabled. 
If the software write lock feature is enabled without disabling the hardware write lock feature, then 
the software write lock feature gets disabled automatically. If the hardware write lock feature is 
selected with the hardware jumper being enabled, the selection is rejected. See Figure  for jumper 
location. For more information on write protection, see Table 38. 
 
Table 38: Write lock 
To  Set the Jumper to: 
Disable the Read and Write lock. 
(In this mode, perform Read and Write 
operation.) 
“OFF” position on the Transducer board. 
 
Enable the Write lock. 
(In this mode, read operation can be performed, 
but the write operation is disabled.) 
 “ON” position on the Transducer board. 
 
8.8  Critical Diagnostics Screens 
When a Critical Diagnostic is present in the Remote Indicator, the Advanced Display will show the 
screen pictured in Figure 24.  This screen will be inserted into the normal screen rotation and 
displayed between the user-defined operator screens.  A description of the diagnostic conditions is 
given Table 39, along with suggested actions for resolving the problem. 
  Electronics Module fault         
 
Figure 24: Local Display Fault Diagnostic Conditions 
Fault Conditions and Recommended Corrective Actions 
Table 39: Fault Conditions and Recommended Corrective Actions. 
Condtion  Analysis 
Recommended 
Corrective Action 
Electronics Module Fault.  
A critical failure has been 
detected on the FF 
Electronics Module. 
Use a FF communicator to read the 
detailed status information from the 
Remote Indicator. Refer to the appropriate 
communicator manual for more information 
about the possible failure causes. 
Cycle power to the 
Remote Indicator. 
If the problem continues 
to occur replace the 
Electronics Module.