Revision 4 Foundation Fieldbus RMA803 Remote Indicator User's Guide Page 41
MAINTENANCE_MODE
It indicates if the device is available for maintenance. When the resource block is in AUTO mode,
MAINTENANCE_MODE parameter displays the text as 'Chk with Oper' i.e., the device is in
process and is not available for maintenance. When the resource block is in OOS mode,
MAINTENANCE_MODE parameter displays the text as ‘Avail for Maint' i.e., the device is out of
process and is available for maintenance. The same text is displayed in the advanced display.
'Chk with Oper'- Check with operator to determine availability.
‘Avail for Maint'- The device is available for maintenance.
Parameter List
Table 15: Resource block parameters
Parameter Description
ST_REV The revision level of the static data associated with the function block.
TAG_DESC The user description of the application of the block.
STRATEGY Used to identify grouping of blocks.
ALERT_KEY The identification number of the plant unit.
MODE_BLK The actual, target, permitted, and normal modes of the block.
BLOCK_ERR Reflects the error status associated with the hardware or software
components associated with a block. It is a bit string, so that multiple errors
may be shown.
RS_STATE Indicates the State of the function block application state machine.
TEST_RW Read/write test parameter is used only for conformance testing.
DD_RESOURCE String identifying the tag of the resource, which contains the Device
Description for the resource.
MANUFAC_ID Manufacturer identification number is used by an interface device to locate
the DD file for the resource.
DEV_TYPE Manufacturer model number associated with the resource. It is used by
interface devices to locate the DD file for the resource.
DEV_REV Manufacturer revision number associated with the resource. It is used by an
interface device to locate the DD file for the resource.
DD_REV Revision of the DD associated with the resource. It is used by the interface
device to locate the DD file for the resource.
GRANT_DENY Options for controlling access of host computer and local control panels to
operating, tuning and alarm parameters of the block.
HARD_TYPES The types of hardware available as channel numbers. The supported
hardware type is SCALAR_INPUT and SCALAR_OUTPUT.
RESTART Allows a manual restart to be initiated.
FEATURES Used to show supported resource block options. The supported features
are: REPORT, SOFT_WRITE_LOCK, HARD_WRITE_LOCK, and
MULTI_BIT_ALARM.
FEATURE_SEL Used to select resource block FEATURE_SEL options

Table of Contents

Other manuals for Honeywell SmartLine RMA800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell SmartLine RMA800 and is the answer not in the manual?

Honeywell SmartLine RMA800 Specifications

General IconGeneral
BrandHoneywell
ModelSmartLine RMA800
CategoryTouch Panel
LanguageEnglish

Related product manuals