Revision 4 Foundation Fieldbus RMA803 Remote Indicator User's Guide Page 105
Problem Cause Things to check Recommended Action
Block alarms are not
reported.
Read FEATURE_SEL.
Reports are not selected in
FEATURE_SEL. If features do not
include Reports then the host must
poll for alarms.
Read LIM_NOTIFY. Set LIM_NOTIFY to a value higher
than zero, but not higher than
MAX_NOTIFY.