Page 76  Foundation Fieldbus RMA803 Remote Indicator User's Guide  Revision 4 
Parameter  Description 
RESET_IN   Resets the totalizers  
STOTAL   Indicates the snapshot of OUT just before a reset  
RTOTAL   Indicates the totalization of “Bad” or “Bad” and “Uncertain” inputs, 
according to INTEG_OPTIONS.  
SRTOTAL   The snapshot of RTOTAL just before a reset  
SSP   The snapshot of TOTAL_SP. 
INTEG_TYPE   Defines the type of counting (up or down) and the type of resetting 
(demand or periodic)  
INTEG_OPTIONS   A bit string to configure the type of input (rate or accumulative) used in 
each input, the flow direction to be considered in the totalization, the 
status to be considered in TOTAL and if the totalization residue must 
be used in the next batch (only when INTEG_TYPE=UP_AUTO or 
DN_AUTO).  
CLOCK_PER   Establishes the period for periodic reset, in hours.  
PRE_TRIP   Adjusts the amount of mass, volume or energy that should set 
OUT_PTRIP when the integration reaches (TOTAL_SP-PRE_TRIP) 
when counting up of PRE_TRIP when counting down.  
N_RESET   Counts the number of resets. It cannot be written or reset.  
PCT_INC   Indicates the percentage of inputs with Good status compared to the 
ones with Bad or Uncertain and Bad status.  
GOOD_LIMIT   Sets the limit for PCT_INC. Below this limit OUT receives the status 
Good  
UNCERTAIN_LIMIT   Sets the limit for PCT_INC. Below this limit OUT receives the status 
Uncertain  
OP_CMD_INT   Operator command RESET Resets the totalizer  
OUTAGE_LIMIT   The maximum tolerated duration for power failure  
RESET_CONFIRM   Momentary discrete value with can be written by a host to enable 
further resets, if the option “Confirm reset” in INTEG_OPTIONS is 
chosen.  
UPDATE_EVT   This alert is generated by any changes to the static data.  
BLOCK_ALM   Used for all configuration, hardware, connection failure, or system 
problems in the block. The cause of the alert is entered in the subcode 
field. The first alert to become active sets the active status in the 
status parameter. As soon as the unreported status is cleared by the 
alert reporting task other block alerts may be reported without clearing 
the Active status, if the subcode has changed.  
LICENSE_STATUS
_IT 
License status of the function block.