Page #42 background image
Configuration
32 UDC3300 Expanded Model: DC330E User Manual 5/00
Function
Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
INP ALG2
Input 2 Algorithm
ATTENTION
All Input
Algorithms operate in
engineering units except
feedforward which
operates in percent of
range units.
NONE LO SEL
W AVG MuDIV
F FWD MULT
FFWDMu MuDIV
AB/C MULT
HI SEL DEW PT
NONE
MATH K2
Weighted Average Ratio or
K Constant for Math
Selections
0.001 to 1000 - -
CALC HI
Calculated Variable High
Scaling Factor for Input
Algorithm 2
999. to 9999. floating
(in engineering units)
- -
CALC LO
Calculated Variable Low
Scaling Factor for Input
Algorithm 2
999. to 9999. floating
(in engineering units)
- -
ALG2 INA
Input Algorithm 2
Input A Selection
INPUT 1 IN AL1
INPUT 2 IN AL2
LP1OUT INPUT 3
LP2OUT
- -
ALG2 INB
Input Algorithm 2
Input B Selection
INPUT 1 IN AL1
INPUT2 IN AL2
LP1OUT INPUT 3
LP2OUT
- -
ALG2 INC
Input Algorithm 2
Input C Selection
NONE LP2OUT
INPUT 1 IN AL1
INPUT 2 IN AL2
LP1OUT INPUT 3
- -
PCT H2
Hydrogen Content for
Dewpoint
1.0 to 99.0% 1.0
ALG2BIAS
Input Algorithm 2 Bias -999 to 9999 floating (in
engineering units)
0.000
8SEG CH1
Eight Segment
Characterizer
If Characterizer 1 is
enabled, the following
Xn VALUE and Yn
VALUE parameters
appear.
DISABL
INPUT1
INPUT2
L1 OUT
L2 OUT
DISABL

Table of Contents

Other manuals for Honeywell UDC3300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell UDC3300 and is the answer not in the manual?

Honeywell UDC3300 Specifications

General IconGeneral
BrandHoneywell
ModelUDC3300
CategoryController
LanguageEnglish

Related product manuals