associated with.. meaning.. ..possible action
Alarms sounded MCC / MCB
(main control card/board)
Sound alarms button has been pressed. -
Alarms Verified MCC / MCB
(main control card/board)
Alarms verify button has been pressed. -
Alarm Zone Disabled /
Enabled at card x
LPC
(loop processor card)
-
Allocation : Double
Allocated card x
number y on loop z
LPC
(loop processor card)
Two devices are given the same address. Loop breaker
(relay contacts) are fused ‘micro welded’ together
(closed) or there is a bad connection.
Check the device wiring. The device may be
faulty, replace if required.
Allocation : Hw fault
card x number y on
loop z
LPC
(loop processor card)
Loop breaker relay has not closed or serial line End-2
is faulty or relay is stuck i.e. closed. The device may
not be correctly fitted.
Check the device wiring. The device may be
faulty, replace if required.
Allocation : Map
error card x number y
on loop z
LPC
(loop processor card)
Loop wiring is incorrect, eg a sub loop may have been
wired on a spur.
Check and rewire if necessary. This fault can
also be device failure.
Allocation : memory
Overflow at card x
number y on loop z
LPC
(loop processor card)
Loop processor has run out of memory during
allocation / when starting a loop.
Software error or more likely a faulty RAM
chip.
Allocation : not
ready at card x
LPC
(loop processor card)
An attempt to allocate a loop when it is already
allocating.
Wait and if it takes longer than 10 minutes then
reset the loop card.
Allocation : OK at
Card n : Allocated x
LPC
(loop processor card)
The loop circuit has been successfully allocated. -
Allocation started
from end 2 at card x
LPC
(loop processor card)
No devices found on End-1 or End 1 of the loop is
open circuit.
Check the wiring to the first device or last
device on the loop.
Allocation : Too many
card x number y on
loop z
LPC
(loop processor card)
Allocated more than 200 devices or the device is
restricted for use with the particular software version.
Replace incompatible devices used on other
systems ie:32000 or SMS device found in
system.
Allocation : Tx fault
card x number y on
loop z
LPC
(loop processor card)
Invalid reply from the device. Check the device. Also check cable routing and
length (measure resistance and capacitance of
cable).
Commissioning instructions
118 4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
Appendix B - Message Action List