Commissioning instructions
32 4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
Vigilon 4/6 loop Panels
Fire Routing LEDs (Post Mid 2015)
The Fire Alarm Routing Equipment FARE red LED works
with FARE Interface configured to operate as a FARE
device. The FARE LEDs illuminate to indicate status of
FARE.
Command Build LEDs CB253 and CB254 (Pre Mid 2015)
The switching of the amber LEDs CB253 or CB254 occurs from a trigger of Command builds 253 or 254. The switching action must be
configured during commissioning.
Example
This example shows how to configure the panel such that by activating an interface input (can be a push button switch), it will cause the
panel LED - CB254 and Master alarms to switch On. If the interface input is released then the panel LED - CB254 and Master alarms will
switch Off.
The following procedures assume a password entry is not required.
# - will appear if a PIN is setup.
Configure Command build trigger:
Press Menu On/Off button and select [SetUp] -> [Usercode]# , momentarily press <etc> to select [SetUp] and [Build], type in the
command build number 254, select [Trigger] and [IO line], type in the interface input channel number, select [Device], type in the interface
device number, select [Loop], type in the loop number and then select [Enter]. The command build 254 is now configured to be triggered by
the interface input.
Configure Command build label:
Press Menu On/Off button and select [SetUp] -> [Usercode]#, momentarily press <etc> to select [SetUp] and [Build], type in the
command build number 254, select [Label] and type in a label of up to 40 characters in length, select [Display] to display the label on the
panel when the command build 254 is triggered.
Configure Command build action:
Press Menu On/Off button and select [SetUp] -> [Usercode]#, momentarily press <etc> to select [SetUp] and [Build], type in the
command build number 254, select [Action] and [Start MA], [Enter], [Reversbl] and [Enter].
Fire
Power
CB253
Sounder
Pre mid 2015
Verify
CB254
Not on BS
panels
Not on BS
panels
Fire
Power
Sounder
Verify
Active
Fault/Dis
Fire Routing O/P
Post mid 2015

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Vigilon 4 loop and is the answer not in the manual?

Honeywell Vigilon 4 loop Specifications

General IconGeneral
BrandHoneywell
ModelVigilon 4 loop
CategoryControl Panel
LanguageEnglish

Related product manuals