4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms. 83
Vigilon 4/6 loops & Compact (VA) panels & network nodes
Installed equipment tests
S Cubed
"
The remote control is only operable when the panel is in the Zone Test
mode for an EN system or Commission mode for a BS system.
¨
Depending on the
type of S-Cubed
device being
commissioned check
to ensure correct
output sound tone,
speech message and
VAD/strobe rate are
given. The S-Cubed
devices should have
been setup using the
commissioning tool.
¨
The volume of the
sounder S-Cubed
device can be
adjusted by using a
remote control.
¨
Each S-Cubed should
be tested for correct
operation in the event
of fire.
¨
The sound levels in
the areas should be
tested in accordance
with the British
Standard
requirements and to
meet the site specific
needs, as agreed with
the customer.
Repeat panel (Loop connected)
Each loop repeat panel should be tested for the following:
¨
System event messages and indications are given
¨
Local fault events, such as Battery and Mains supply disconnection
¨
Alarm controls & Cancel Buzzer operation is possible
Mimic Panel
Each Mimic indicator panel should be configured and tested for the following:
¨
To confirm fires are indicated
¨
Local fault events, such as Battery and Mains supply disconnection
¨
Lamp Test
On an A3 Mimic panel by pressing the button on the centre face of the unit
On an A2 mimic panel (Legacy panel) by operating the test key
On an A4 mimic panel (legacy panel) by inserting a 2mm pin like object (for example a
small terminal screwdriver) into a hole located on the underside of the panel enclosure.
Mains powered DAU and micro DAU (Legacy devices)
Each Mains powered DAU and micro DAU should be configured and tested for the following:
¨
Check to ensure correct output sound tone and speech message are given of fire events.
¨
Adjust the volume out at speakers on the Speaker circuits using controls on the Mains
powered DAU in accordance with the British Standard requirements and to meet the site
specific needs as agreed with the customer.
Similarly volume level should be adjusted at each micro DAU to the required setting during
commissioning.
VIGILON Compact VA system (Legacy system)
¨
A 'Fall back' test must be performed to ensure the central messages are announced. This is
achieved by stopping the two loops using the [Test/Eng] menu and then by conducting a
Sound Alarm from the panel. Restart the loop on completion of the test.
Deviations from standards
¨
The results of system tests carried out must be in accordance with the relevant standards
and project specification.
¨
Any deviations must be documented and reported for approval.
Thinned
section
on base
3m - maximum range
Press the function button to toggle between:
function and note the Red LED flashes x2 every 2 secondsTone
Volume function and note the Red LED flashes x1 every 2 seconds
Press the button to increase or to select the next
Press the button to decrease or to select the previous
volume tone
volume tone
+
-
Wall
Sounder device
+
-
Red LED
Flash
Steady On
Perform a short press on the Power button
to turn On the remote control. The Red LED will
flash x1 every 2 seconds
Off
Press and hold the Power button to save the adjustments made.
The Red LED will remain On whilst the button is held pressed.
The data is saved to the device when the tone/speech on the S-Cubed unit
stops briefly. Release the button on the remote control and the
Red LED will switch Off to complete the adjustment process.
Note: The VAD/strobe light on the S-Cubed unit if fitted will flash rapidly when
the volume is being adjusted using the remote control.
Remote Control
Trouble shooting
If the remote control fails to operate in close
proximity to the thinned section of the Sounder
device, then a possible cause may be
discharged battery. In which case replace the
battery.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Vigilon 4 loop and is the answer not in the manual?

Honeywell Vigilon 4 loop Specifications

General IconGeneral
BrandHoneywell
ModelVigilon 4 loop
CategoryControl Panel
LanguageEnglish

Related product manuals