Checking device STATUS
Loop Device Status
To list the STATUS of a device on an allocated loop at the Control Panel: Press Menu On/Off
button and then select [Info], momentarily press <etc> to select [Status] -> [Device], enter the
device number, select [Loop], enter the loop number n on which the device resides, select [Enter]
to view device status information.
Analogue Channel 1 is forward scatter optical smoke sensor
Analogue Channel 2 is heat sensor
Analogue Channel 3 is for CO gas sensor
Analogue Channel 4 is for backward scatter optical smoke sensor
Analogue Channel 5 reports sounder/flasher/speech faults to the control panel
Analogue Channel 6 reports monitored input/monitored output faults to the control panel
O - Output, I - Input and . signify - not used
Device digitalI/O channels
S4 Dual OH/Red VAD O..O 1,2,4,5
S4 Heat/Voice Sen Sndr/Red VAD OOOO 2, 5
S4 Dual OH/Voice Sen Sndr/Red VAD . OOO 1, 2, 4, 5
S4 Dual OH/CO/Voice Sen Sndr/Red VAD OOOO 1, 2, 3, 4, 5
S4 Dual OH/White VAD O . . O 1, 2, 4, 5
S4 Dual OH/White VAD (HP) O . . O 1, 2, 4, 5
S4 Dual OH/Voice Sndr/White VAD (Std) OOOO 1, 2, 4, 5
S4 Dual OH/Voice Sen Sndr/White VAD (HP) OOOO 1, 2, 4, 5
S4 Heat/Voice Sndr/White VAD (HP) OOOO 2, 5
S4 Dual OH CO/Voice Sen Sndr / White VAD (HP) OOOO 1, 2, 3, 4, 5
S4 Dual OH/Voice Sounder . OOO 1, 2, 4, 5
S4 OH Sensor Sounder . OOO 1, 2, 5
S4 Dual OH Sensor Sounder . OOO 1, 2, 4, 5
S4 Heat Sensor Sounder . OOO 2, 5
S4 Dual OH CO Sensor . . . O 1, 2, 3, 4, 5
S4 Heat Sensor . . . O 2
S4 Heat Sensor Sounder . OOO 2, 5
S4 Dual Optical Heat Sensor . . . O 1, 2, 4
S4 Dual Optical Heat Sensor CO ...O 1,2,3,4,5
S4 Dual Optical Heat Sensor Sounder . OOO 1, 2, 4, 5
+ Monitored input 6
+ Monitored output 6
Other devices
Beam transmitter . . . O 2
Beam receiver . . . O 1- raw data
2- average
data
4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms. 65
Vigilon 4/6 loops & Compact (VA) panels & network nodes
Checking device STATUS
Loop 1 No. 7 Dual optical/Heat/CO
LB1:C End1:Hi End2:Hi
I/O:...0 Anal:1-4
2nd:250 3rd:0 Short delay:0
Zone 1 Zone 1
LED)
,6
Loop on which
the device is installed
Location of the
device on the loop
Device description
Monitored Input / LED is
attached to the device
Loop breaker
condition
C:closed
Status of End 1
of the device
(high or low)
Status of End 2
of the device
(high or low)
Digital
Input outputs
Analogue channels
used
1:Optical (forward)
2:Heat
3:Gas
4:Optical (Backward)
5:Sounder/VAD (Strobe)/Speech fault
6:Monitored line or LED
Secondary address
denotes group of devices
Tertiary address
used primarily by
sounders/VAD (strobe)
Short circuit delay
associated with
number of T breakers
off T breakers
Zone number and label