Commissioning instructions
78 4188-856_issue 7_07/15_Generic Vigilon (Compact + VA) Comms.
Interface Unit STATES
Interface Unit STATES
Single channel interface input STATES
These STATES also apply to loop powered single channel interface.
STATE Definition Application
State 0 Default - all
Inputs enabled
Normal use
State 1 Input 1 disabled Selective disablement and
enablement of interface input circuits
Where an input circuit is used for fire
detection application, the call points
on the circuits will NOT remain
operational on disablement of the
circuit.
State 15 All inputs
disabled
Interface input disablement
4 - Channel Interface Unit STATES
These 4 - channel interface unit input STATES are applicable for both mains and loop powered
interface units.
STATE Definition Applications
State 0 Default - all Inputs enabled Normal use
State 1 Input 1 disabled Selective disablement and
enablement of interface input
circuits
"
Where an input
circuit is used for fire
detection application, the
call points on the loop
circuit will remain
operational on disablement
of the loop circuit.
State 2 Input 2 disabled
State 3 Inputs 1 and 2 disabled
State 4 Input 3 disabled
State 5 Inputs 1 and 3 disabled
State 6 Inputs 2 and 3 disabled
State 7 Inputs 1, 2 and 3 disabled
State 8 Input 4 disabled
State 9 Inputs 1 and 4 disabled
State 10 Inputs 2 and 4 disabled
State 11 Input 1, 2 and 4 disabled
State 12 Inputs 3 and 4 disabled
State 13 Inputs 1, 3 and 4 disabled
State 14 Inputs 2, 3 and 4 disabled
State 15 All inputs disabled interface input disablement