EasyManua.ls Logo

Honeywell XNX - Page 102

Honeywell XNX
200 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
XNX Universal Transmitter
Section 3 - Calibration
100
3.4 Calibrate mA Output
UseCalibratemAOutputtoadjustthemilliampoutputtoprovide
thecorrectoutputlevelsatperipheraldevicesconnectedtothe
transmitter
Figure 219. Calibrate mA Output Menu
Toadjustthe4mAoutput,usethe
switchestoincreaseor
decreasetheoutput,thenuse
toacceptthenewvalueand
movetothe20mAsettingor
todiscardtheselectionand
returntothepreviousmenu�

Figure 220. Calibrate mA Output Screens
Duringinstallation,anmAmetermustbeconnectedinseries
withthe4-20mAloopasshownbelow
Control Equipment
XNX
mA
Meter
4-20 mA loop
4-20 mA loop
Remote end
R load
Figure 221. 4-20 mA loop with mA meter
Note: CalibratedmAoutputisrequiredforproperoperationofinternal
diagnostics.
AnF165faultwillbereportedifthe4-20mAcalibrationfails�
3.5 Align Excel (Searchline Excel)
Figure 222. Align Excel Menu
FordetailedinformationonAligningtheSearchlineExcel,seethe
SearchlineExcelTechnicalManual(P/N:H-MAN0530-V1)�
Alignment Bargraph
Signal Strength
1.00 Signal Strength Target
Reference Value
Figure 223. Align Excel Screen
AligntheunitusingtheinformationfoundintheSearchlineExcel
manual�Asthealignmentisperformed,thetransmitterdisplaywill
indicatethesignalstrengthintheformofabargraph�Alignthe
Exceluntilthesignalstrengthbargraphreachesorexceeds1�00as
shownonthedisplay�

Table of Contents

Other manuals for Honeywell XNX

Related product manuals