EasyManua.ls Logo

Honeywell XNX - 5�2 Fault Messages

Honeywell XNX
200 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
XNX Universal Transmitter
Section 5 - Warnings/Faults
113
5.2 Fault Messages
Fault Description
Appli-
cable
Sensors
Latching / Non-
Latching
Frequency of
Diagnostic
Event History Data Action For Resolution
F101
UnexpectedSen-
sorReset
All Non-latching
ECC&mV:main
loopx2;
Optima&Excel:2
seconds
Note2�Optimaor
Excel:Sensorfaultor
warningcode(Note4)
Ifrepeated,checksupplyvoltage,checkcableloopimpedance,check
terminalconnections
F103
XNXTemperature
Error
All Non-latching 2seconds
XNXtemperature
(Celsius)
Checklocationforheatsources�Fitwithsunshadeorotherprotec-
tion�Changethetransmitter’slocation�ChecktemperatureinInfo-
>TransmitterStatustoensuretemperatureisbeingmeasuredproperly
F104
XNX24VDCSup-
plyBad
All Non-latching 2seconds
XNXsupplyvoltage
x1000
Checkthewireofthe24Vpowersupplytothetransmitterandthepower
supplyoperation�
F105
3�3VDCSupply
BadonXNX,per-
sonalityboard,or
optionboard
All Non-latching 2seconds
1=XNX,
2=Personalityboard,
3=Optionboard
CheckTransmitterStatus
F106
XNXRealTime
ClockFailure
All Non-latching 2seconds
Totalsecondssince
Jan1,1970
Eitherclockwasincorrectlysetorthebatteryfortheclockhasfailed�
Note:theclockwillstoprunningonJanuary1,2036�
F107
XNXInternalFail-
ure(RAM,ROM,
EEPROM,Opcode)
All
Non-latchingex-
ceptforEEPROM
error
Atpowerupand
8hours
Note3 ContactHoneywellAnalytics’ServiceDepartment�
F108
XNXmAOutput
LoopFailure
All Latching 2seconds
mAoutputerror(mea-
suredmA-setmA)
CheckwiringofmAoutputfromXNX�CheckthatswitchesS1andS2are
setcorrectly�NotethatifF108isnotresolvedquickly,anF149(Internal
CommunicationFailure-mA)willalsobegenerated�Whenthecauseof
F108isresolved,boththeF108andF149willbecleared�
F109
SimulatedWarn-
ing/Fault
All Non-latching Enabledbyuser 0 Performinganalarm/faultresetwillclearallsimulation�
F110
Sensorsoftware
mismatch
Optima Latching
Onlycheckedat
powerup
Sensorrmwarever-
sionx10
ContactHoneywellAnalytics’ServiceDepartment�
F111
NegativeDrift ECC,mV Non-latching 2seconds
Rawgasconcentra-
tionofsensor
Checksensorlocationforexternalinterference�Performzerocalibra-
tion�Ifproblempersistsafterzerocalibrationandnointerferenceexists,
replacesensor
NegativeDrift;may
indicateafailedIR
sensor
Optima,
Excel
Non-latching
XNXpollssensor
every2seconds,
diagnosticfre-
quencycontrolled
bysensor
Sensorfaultorwarn-
ingcode
Checksensorlocationforexternalinterference�Performzerocalibra-
tion�Ifproblempersistsafterzerocalibrationandnointerferenceexists,
replacesensor

Table of Contents

Other manuals for Honeywell XNX

Related product manuals