EasyManuals Logo

Honeywell XNX Technical Manual

Honeywell XNX
200 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #72 background imageLoading...
Page #72 background image
XNX Universal Transmitter
Section 2 - Installation and Operation
70
Figure 97. Setting Alarm Latching/Unlatching
UsethesameproceduretosetthedesiredvaluesforAlarm
2andFaults�Whenallsettingshavebeenmade,use
to
navigatetothe
onthedisplay�Use
toacceptsettings�
Figure 98. Accept Settings
Whenthesettingshavebeensaved,thefollowingscreenis
displayed�
Figure 99. Settings Accepted Screen
Note: Whennon-latchingisselected,externalalarmlatchingis
recommended.
Set Units
TheSetUnitsmenuallowstheunitsofmeasurementdisplayed
ontheXNXmainmenutobeset�Thisoptionalsosetstheunits
transmittedviaHART,Modbus,orFoundationFieldbussensors
attachedtotheXNXtransmitter,reportingconcentrationsinPPM
or%VOL(exceptoxygen)�
Figure 100. Set Units Menu
Tochangetheunits,usethe switchestohighlighttheunits
icon�Use
toselectit�Thetransmitter’sdisplaywillchange
totheDisplayUnitSelectionscreenwhichshowstheavailable
choicesforthesensortypeinstalled�Usethe switchesto
highlightthedesiredunitofmeasurement�Use
toselectitor
todiscardtheselection�

Figure 101. Display Unit Selection Screen
Caution:Whenchangingunitsofmeasure,checkalarmlevel
settingsfortheproperunitsandchangeasnecessary.
Oncetheunitsofmeasurementhavebeenset,usethe
switchestonavigatetothe‘ü’toacceptthevalues�
mA Levels
ThisoptionallowstheusertoselectmAoutputlevelsforinhibit,
fault,andoverrange�Beamblockandlowsignalapplyto

Table of Contents

Other manuals for Honeywell XNX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell XNX and is the answer not in the manual?

Honeywell XNX Specifications

General IconGeneral
Ingress ProtectionIP66/67
Product TypeUniversal Transmitter
Enclosure RatingIP66/67
DisplayLCD
Communication ProtocolsHART, Modbus, Foundation Fieldbus
Power Supply24 VDC nominal, 18-32 VDC
Operating Temperature-40°C to +65°C (-40°F to +149°F)
MaterialAluminum or Stainless Steel
Gas TypesToxic, Oxygen, and Combustible gases
Output4-20 mA
Relays3 programmable relays
ApprovalsATEX, IECEx, UL, CSA
Sensor CompatibilityElectrochemical, catalytic, infrared, and other sensor types

Related product manuals