EasyManua.ls Logo

Honeywell XNX - Set Units; Ma Levels

Honeywell XNX
200 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
XNX Universal Transmitter
Section 2 - Installation and Operation
70
Figure 97. Setting Alarm Latching/Unlatching
UsethesameproceduretosetthedesiredvaluesforAlarm
2andFaults�Whenallsettingshavebeenmade,use
to
navigatetothe
onthedisplay�Use
toacceptsettings�
Figure 98. Accept Settings
Whenthesettingshavebeensaved,thefollowingscreenis
displayed�
Figure 99. Settings Accepted Screen
Note: Whennon-latchingisselected,externalalarmlatchingis
recommended.
Set Units
TheSetUnitsmenuallowstheunitsofmeasurementdisplayed
ontheXNXmainmenutobeset�Thisoptionalsosetstheunits
transmittedviaHART,Modbus,orFoundationFieldbussensors
attachedtotheXNXtransmitter,reportingconcentrationsinPPM
or%VOL(exceptoxygen)�
Figure 100. Set Units Menu
Tochangetheunits,usethe switchestohighlighttheunits
icon�Use
toselectit�Thetransmitter’sdisplaywillchange
totheDisplayUnitSelectionscreenwhichshowstheavailable
choicesforthesensortypeinstalled�Usethe switchesto
highlightthedesiredunitofmeasurement�Use
toselectitor
todiscardtheselection�

Figure 101. Display Unit Selection Screen
Caution:Whenchangingunitsofmeasure,checkalarmlevel
settingsfortheproperunitsandchangeasnecessary.
Oncetheunitsofmeasurementhavebeenset,usethe
switchestonavigatetothe‘ü’toacceptthevalues�
mA Levels
ThisoptionallowstheusertoselectmAoutputlevelsforinhibit,
fault,andoverrange�Beamblockandlowsignalapplyto

Table of Contents

Other manuals for Honeywell XNX

Related product manuals