XNX Universal Transmitter
Section 6 - Specications
143
6.2.7 EN60079-29-1 Performance Approved Gases for mV Sensor Types
Sensor Type
EN60079-29-1
Reference
Veried Gas Selections
Hydrogen Methane-2 Propane-2 Butane-2 Star 2 Star 4
MPD AMCB1
Standard Test Gas
l l
Other Gases
l l
n-nonane
SP-HT
Standard Test Gas
l l
Other Gases
l l
n-nonane
Max Zero Deviation (see note 1) -7% LEL -9% LEL -7% LEL
LDL (see note 2) 3% LEL 5% LEL 3% LEL
NOTES:
1� Readings<0%LELarenotdisplayedorindicatedonthe20mAoutput�ValuesexceedingthezerodeviationlimitwillresultinF111faults�
2� Readings<LDLareshownas0%onthedisplayand20mAoutput�
6.2.8 Other Sensor Performance Data
Performancedataforothersupportedsensorsisavailableintheirrespectivetechnicalmanuals�

Table of Contents

Other manuals for Honeywell XNX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell XNX and is the answer not in the manual?

Honeywell XNX Specifications

General IconGeneral
Ingress ProtectionIP66/67
Product TypeUniversal Transmitter
Enclosure RatingIP66/67
DisplayLCD
Communication ProtocolsHART, Modbus, Foundation Fieldbus
Power Supply24 VDC nominal, 18-32 VDC
Operating Temperature-40°C to +65°C (-40°F to +149°F)
MaterialAluminum or Stainless Steel
Gas TypesToxic, Oxygen, and Combustible gases
Output4-20 mA
Relays3 programmable relays
ApprovalsATEX, IECEx, UL, CSA
Sensor CompatibilityElectrochemical, catalytic, infrared, and other sensor types