XNX Universal Transmitter
Section 5 - Warnings/Faults
108
5.1 Warning Messages
Warning Description
Applicable
Sensors
Latching / Non-Latching
Frequency of Diag-
nostic
Event History Data Action For Resolution
W001
XNX
®
24VDC
SupplyBad
All Non-latching 2seconds
XNXsupply
voltagex1000
Checkwireof24VpowersupplytoXNXaswellaspowersupplyopera-
tion�
W002
XNXTempera-
tureError
All Non-latching 2seconds
XNXtempera-
ture(Celsius)
Checklocationforheatsources�Fitwithsunshadeorotherprotection�
ChangelocationofXNX�ChecktemperatureinInfo->TransmitterStatus
toensuretemperatureisbeingmeasuredproperly
W003
Simulated
Warning/Fault
All Non-latching Enabledbyuser 0 Performinganalarm/faultresetwillclearallsimulation�
W005
SensorTem-
peratureError
Optima Non-latching
XNXpollssensor
every2seconds,
diagnosticfre-
quencycontrolled
bysensor
Sensorfaultor
warningcode
(Note4)
Checklocationforheatsources�Fitwithsunshadeorotherprotection�
ChangelocationofXNX�ChecktemperatureinInfo->SensorStatusto
ensuretemperatureisbeingmeasuredproperly
SensorTem-
peratureError
Excel Non-latching
XNXpollssensor
every2seconds,
diagnosticfre-
quencycontrolled
bysensor
Sensorfaultor
warningcode
(Note4)
Checklocationforheatsources�Fitwithsunshadeorotherprotection�
ChangelocationofXNX�ChecktemperatureinInfo->SensorStatusto
ensuretemperatureisbeingmeasuredproperly
SensorTem-
peratureError
ECC Non-latching 2seconds
Sensortemper-
ature(Celsius)
Checklocationforheatsources�Fitwithsunshadeorotherprotection�
ChangelocationofXNX�ChecktemperatureinInfo->SensorStatusto
ensuretemperatureisbeingmeasuredproperly
W006
NegativeDrift ECC,mV Non-latching 2seconds
Rawgascon-
centrationof
sensor
Checksensorlocationforexternalinterference�Performzerocalibra-
tion�Ifproblempersistsafterzerocalibrationandnointerferenceexists,
replacesensor
NegativeDrift
Optima,
Excel
Non-latching
XNXpollssensor
every2seconds,
diagnosticfre-
quencycontrolled
bysensor
Sensorfaultor
warningcode
Checksensorlocationforexternalinterference�Performzerocalibra-
tion�Ifproblempersistsafterzerocalibrationandnointerferenceexists,
replacesensor
W007
Calibration
Required
All Non-latching 2seconds
Numberofdays
remaininguntil
calibrationex-
pires,negative
=numberof
daysexpired
Timesincethelastspancalibrationhasexceededadenedlimit�Per-
formingasuccessfulspancalibrationwillclearthecondition�Thelimitis
theuser-denedcalibrationinterval�W007canbedisabledbysettingthe
calibrationintervalto0�

Table of Contents

Other manuals for Honeywell XNX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell XNX and is the answer not in the manual?

Honeywell XNX Specifications

General IconGeneral
Ingress ProtectionIP66/67
Product TypeUniversal Transmitter
Enclosure RatingIP66/67
DisplayLCD
Communication ProtocolsHART, Modbus, Foundation Fieldbus
Power Supply24 VDC nominal, 18-32 VDC
Operating Temperature-40°C to +65°C (-40°F to +149°F)
MaterialAluminum or Stainless Steel
Gas TypesToxic, Oxygen, and Combustible gases
Output4-20 mA
Relays3 programmable relays
ApprovalsATEX, IECEx, UL, CSA
Sensor CompatibilityElectrochemical, catalytic, infrared, and other sensor types