XNX Universal Transmitter
Section 2 - Installation and Operation
30
2.2 Wiring the XNX Transmitter
TheXNXtransmitterisavailableinsensortechnologies,or
personalityoptions,whichsupportavarietyofsensorsand
applications�Eachofthepersonalitiesusededicatedinterface
boards�Pluggableterminalblocksareusedforeasyconnection
andservice�Thepersonalityboardsandoptionalcommunication
interfacesareenclosedinplastichousingscomprisingthe
electronicsPOD(Personality,Options,andDisplay)�The
PersonalitycircuitboarddeterminestheXNXbehaviorbasedon
thesensortypeattachedtotheXNXinterface(Figure35)�See
Specicationsfordriftandzerodeviationvalues�
ThistableillustratesthethreeXNXtransmittercongurations
andthesensorseachsupport�
XNX IR Personality XNX EC Personality
SearchlineExcel
SearchpointOptimaPlusLocal/
Remote
XNXECSensor
GenericmASensors XNXECSensorRemoteMountKit
XNX mV Personality
705Local/Remote MPDLocal(catbeadandIR) SensepointLocal/Remote
705HTLocal/Remote MPDRemote SensepointPPMLocal/Remote
SensepointHTRemote
Figure 28. XNX Transmitter personalities
Caution: Beforewiringthetransmitter,confirmthatthecorrect
personalityandcommunicationboardsareinstalled.
2.2.1 General Wiring Considerations
ForproperoperationoftheXNXUniversalTransmitterand
sensortechnologies,considerationofwiring-inducedvoltage
drops,transientelectricalnoise,anddissimilarearthground
potentialsisimperativeinthedesignandinstallationofthe
system�
EMI note for applications using shielded cable: Cable
shieldmustprovide90%coverageofthewiring�Cable
shieldterminationsmustbemadeatthecableglands
withsuitableEMI-typeglands�Avoidterminating
cableshieldsattheearthgroundluginsidetheXNX
enclosure�
Loading
WhenwiringforDCpower,4-20mAsignal,remotewiringto
sensorsmustbesizedsufcientlytoprovideadequatevoltages
forthelinelengthandtheloadsthatwillbeused�
Isolation
Isolatingpowerandsignalcarryingconductorsisrecommended�
Circuit Protection
Supplycircuitsmustprovideovercurrentprotection�Class2
powersuppliesarerequiredfor24voltDCsupply�Consider
inrushcurrentinspecifyinganyDCsupply�Powersupplyrange

Table of Contents

Other manuals for Honeywell XNX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell XNX and is the answer not in the manual?

Honeywell XNX Specifications

General IconGeneral
Ingress ProtectionIP66/67
Product TypeUniversal Transmitter
Enclosure RatingIP66/67
DisplayLCD
Communication ProtocolsHART, Modbus, Foundation Fieldbus
Power Supply24 VDC nominal, 18-32 VDC
Operating Temperature-40°C to +65°C (-40°F to +149°F)
MaterialAluminum or Stainless Steel
Gas TypesToxic, Oxygen, and Combustible gases
Output4-20 mA
Relays3 programmable relays
ApprovalsATEX, IECEx, UL, CSA
Sensor CompatibilityElectrochemical, catalytic, infrared, and other sensor types